29
Settings
menu 5
10
10
For precise setting of the charging priorities for systems with multiple storage
tanks, the necessary temperature increase of the collector at which the interrup-
tion of the charging in the lower-priority storage tank is extended by one minute
is set here. The interruption is extended because the temperature increase of
the collector is expected to enable charging in the higher-priority storage tank
soon. If the rise in temperature falls below the set value, then the charging of
the lower-priority storage tank is enabled again.
Setting range: from 1
°
C to 10
°
C/default setting: 3
°
C
10.17 Increase
menu 5.x
= temperature increase during the charging pause
10.18 Table: Programs (hydraulic variants) with associated settings
The table lists the settings corresponding to the speci
fi
c programs (hydraulic
variants). The reference sensors 1-5 corresponding to the functions are la-
belled S1-S5. The switch outputs (relays) corresponding to the functions
for pumps and valves are labelled with R1 or R2.
1
2
3
4
5
6
Tmin S1
S1
=>R1
S1
=>R1
S1
=>R1
S1
=>R1
S1
=>R1
S1
=>R1
Tmin S5
S5
=>R2
S5
=>R2
Tmax S2
S2
=>R1
S2
=>R1
S2
=>R1
S2
=>R1
S2
=>R1
S2
=>R1
Tmax S4
S4
=>R2
S4
=>R2
S4
=>R2
S4
=>R2
Δ
T R1
S1/S2
=>R1
S1/S2
=>R1
S1/S2
=>R1
S1/S2
=>R1
S1/S2
=>R1
S1/S2
=>R1
Δ
T R2
S5/S4
=>R2
S5/S4
=>R2
S1/S4
=>R1+R2
S1/S4
=>R2
Tset S3
S3
=>R3
S3
=>R3
S3
=>R3
S3
=>R3
S3
=>R3
S3
=>R3
Hyst. S3
S3
=>R3
S3
=>R3
S3
=>R3
S3
=>R3
S3
=>R3
S3
=>R3
Energy savings
mode
möglich
=>R3
möglich
=>R3
möglich
=>R3
möglich
=>R3
möglich
=>R3
möglich
=>R3
Tmin S3
S3
=>R3
S3
=>R3
S3
=>R3
S3
=>R3
S3
=>R3
S3
=>R3
Tset S4
S4
=>R2
S4
=>R2
Hyst. S4
S4
=>R2
S4
=>R2
priority sensor
S2 o. S4
=>R1/R2
S2 o. S4
=>R1/R2