10. Settings
Settings
menu 5
10
10
Caution
Caution
This does not under any
circumstances replace the
safety facilities to be pro-
vided by the customer!
The menu is closed by pressing
“esc” or selecting “Exit settings”.
Various settings can be made depending on the selection of hydrau-
lic variant 1-6. This is explained in more detail in Table 10.18. This
table also indicates the associated reference sensors and switch
outputs. The following pages contain generally valid descriptions
for the settings.
The necessary basic settings
required for the control function are
made in menu “5. Settings”.
10.1 Tmin S1
menu 5.x
= enable/start temperature at sensor 1
If this value is exceeded at sensor 1 and the other conditions are also met,
then the controller switches the associated pump and/or valve on. If the
temperature at sensor 1 drops below this value by 5°C, then the pump
and/ or the valve are switched off again.
Setting range: from 0°C to 99°C/default setting: 20°C
10.2 Tmin S5
menu 5.x
= enable/start temperature at sensor 5
If this value is exceeded at sensor 5 and the other conditions are also met,
then the controller switches the associated pump and/or valve on. If the
temperature at sensor 5 drops below this value by 5°C, then the pump
and/ or the valve are switched off again.
Setting range: from 0°C to 99°C/default setting: 40°C
Danger!
Temperature values which are set too high can lead to scalding
or damage to the system. Scalding protection must be provided
by the customer!
10.3 Tmax S2
menu 5.x
= switch-off temperature at sensor 2
If this value is exceeded at sensor 2 and the other conditions are also met,
then the controller switches the associated pump and/or valve off. If sensor
2 falls below this value again and the other conditions are also met, then
the controller switches the pump and/or valve on again.
Setting range: from 0°C to 99°C/default setting: 60°C