43
(LED fl ashes +
warning symbol)
Z.1. Malfunctions with error messages
Malfunctions
If the controller detects a malfunction, the
red light fl ashes and the warning symbol
also appears in the display. If the error
is no longer present, the warning symbol
changes to an info symbol and the red light
no longer fl ashes.
To obtain more detailed information on the
error, press the key under the warning or
info symbol.
Danger
Do not try to deal with this
yourself. Consult a specialist in
the event of an error!
Possible error messages:
Notes for the specialist:
Sensor x defective
Means that either the sensor, the sensor input at the
controller or the connecting cable is/was defective.
(Resistance table see „B.2. - Temperature resistance
table for Pt1000 sensors“)
Collector alarm
Means that the collector has fallen/fell below the
temperature set under menu „5.6. - Collector alarm“
Restart
Means that the controller was restarted, for example
due to a power failure. Check the date&time!
Time & Date
This message appears automatically after a mains
failure because the time & date have to be checked,
and reset if necessary.
No fl ow
Is displayed when ∆T between storage and collector
is 50 °C or higher for 5 minutes without interruption.
Frequent on / off
A relay was switched on and off more than 5 times
within 5 minutes.
AL failed
Is displayed when AL ref -5 °C was not measured for
the set Al residence time at the AL sensor.