24
Special functions
Menu “6. Special functions” is used to set basic
items and expanded functions.
The menu is closed by pressing “esc” or select-
ing “Exit special functions”.
6. - Special functions
Caution
Other than the time all settings may
only be made by a specialist.
The suitable hydraulic variant for the specifi c application is selected and set here (see
B.5 Hydraulic variants). The associated diagram can be displayed by pressing “info”.
6.1. - Program selections
Caution
Normally the program selection is made only once during initial com-
missioning by the specialist. Incorrect program selection can lead to
unpredictable errors.
Caution
If the program is changed, the settings revert to factory settings.
This menu contains the settings for the speed controlled output V1.
6.2. - Signal V1
6.2.1. - Type of pump
The type of speed controlled pump must be entered here.
Standard
: Speed control for standard pumps.
0-10V
: Speed control of e.g. High effi cency pumps by 0-10V signal.
PWM
: Speed control of e.g. High effi cency pumps by PWM signal.
In this menu, preconfi gured profi les for various pumps can be selected. Please note
that individual settings are still possible even when a profi le has been selected.
This menu determines the type of pump used: Solar pumps perform at their highest
power when the signal is also maxed, heating pump on the other hand are set to high-
est power wenn the control signal is at the lowest. Solar = normal, heating = Inverted.
6.2.2. - Pump
6.2.3. - Output Signal