26
Special functions
6.3. - Speed control
6.3.1. - Modes
The following speed variants are available here:
Off:
There is no speed control. The connected pump is only switched on or off with full
speed.
Mode 1:
After the purging time the controller switches to the set max. speed. If the
temperature difference Set ∆T between the reference sensors (collector and storage
tank) is less than the set value, then the speed is decreased by one stage after the
control time elapses. If the temperature difference between the reference sensors is
greater than the set value, then the speed is increased by one stage after the control
time elapses. If the controller has adjusted the speed of the pump down to the smallest
stage and the Set ∆T between the reference sensors is ∆T off, the pump is switched
off.
Mode 2:
After the purging time the controller switches to the set min. speed. If the
temperature difference Set ∆T between the reference sensors (collector and storage
tank) is greater than the set value, then the speed is increased by one stage after the
control time elapses. If the temperature difference Set ∆T between the reference sen-
sors is below the set value, then the speed is decreased by one stage after the control
time elapses. If the controller has adjusted the speed of the pump down to the smallest
stage and the ∆T between the reference sensors is T∆off, the pump is switched off.
Mode 3:
After the purging time the controller switches to the set min. speed. If the
temperature at the reference sensor (collector) is greater than the setpoint to be set
subsequently, then the speed is increased by one stage after the control time expires.
If the temperature at the reference sensor (collector) is less than the setpoint to be set
subsequently, then the speed is decreased by one stage after the control time expires.
Mode 4:
When the primary storage is loaded, speed control works as in V3.
When the secondary storage is loaded, speed control works as in V2.
With speed control the MTDC
makes it possible to vary the speed of connected
pumps.
This function should only be activated by a specialist. Depending on the
pump and pump stage used, the minimum speed should not be set too
low, because otherwise the pump or the system may be damaged. The
information provided by the relevant manufacturer must also be observed!
If in doubt, the min. speed and the pump stage should generally be set to
high rather than too low.
Caution