Setting Your NetExtender Address Range
The NetExtender address range defines the IP address pool from which addresses will be assigned to
remote users during NetExtender sessions. The range needs to be large enough to accommodate the
maximum number of concurrent NetExtender users you wish to support.
The range should fall within the same subnet as the interface to which the SMA appliance is connected, and
it must not overlap or collide with any assigned addresses if other hosts are on the same segment as the
SMA appliance.
Determine the correct subnet based on your network scenario selection:
Scenario
A
192.168.200.100
to
192.168.200.200
(default range)
Scenario
B
Select a range that falls within your existing DMZ subnet. For example, if your DMZ uses the
10.1.1.0/24
subnet, and you want to support up to 30 concurrent NetExtender sessions,
you could use
10.1.1.220
to
10.1.1.249
.
Scenario
C
Select a range that falls within your existing LAN subnet. For example, if your LAN uses the
192.168.168.0/24
subnet, and you want to support up to 10 concurrent NetExtender
sessions, you could use
192.168.168.240
to
192.168.168.249
.
NOTE:
DHCP/DHCPv6 is supported and can manage the IPv4 and IPv6 addresses in the LAN and the
NetExtender client address ranges.
To set your NetExtender address range:
1. Using Secure Mobile Access, navigate to the
Clients > Settings
page.
2. Enter an address range in the
Client Address Range Begin
and
Client Address Range End
fields.
3. Click
Accept
to add the
Client Address Range
.
Scenario A
192.168.200.100
to
192.168.200.200
(default range)
Scenario B
An unused range within your DMZ subnet.
Scenario C
An unused range within your LAN subnet.
If you do not have enough available addresses to support your desired number of concurrent NetExtender
users, you may use a new subnet for NetExtender. This condition may occur if your existing DMZ or LAN is
configured in NAT mode with a small subnet space, such as
255.255.255.224
, or more commonly if your
DMZ or LAN is configured in Transparent mode and you have a limited number of public addresses from
your ISP. In either case, you may assign a new, unallocated IP range to NetExtender (such as
192.168.10.100
to
192.168.10.200
) and configure a route to this range on your gateway appliance.
For example, if your current Transparent range is
67.115.118.75
through
67.115.118.80
, and you wish to
support 50 concurrent NetExtender clients, configure your SMA X0 interface with an available IP address in
the Transparent range, such as
67.115.118.80
, and configure your NetExtender range as
192.168.10.100
to
192.168.10.200
. Then, on your gateway device, configure a static route to
192.168.10.0
, using
67.115.118.80
.
SMA 10.2 Deployment Guide for the SMA 100 Series
Additional Configuration
19