PARAMETER SETTING MENU (PArAM)
Press
"OK"
to display one of the following submenus:
Display
By default
Description
Automatic closure
time
(tcA)
10 s
Setting the automatic closure time (if tcA is active in LoGic).
Automatic closure time setting from 3 to 120 s.
Motor 1 torque
(R1t)
50 %
Setting the minimum torque value for motor 1 required to move the gate.
Motor 1 torque setting value between 1% and 99%.
Motor 2 torque
(R2t)
50 %
Setting the minimum torque value for motor 2 required to move the gate.
Motor 2 torque setting value between 1% and 99%.
Motor 1 slowing down
torque
(R1t SLoW)
45 %
Setting the torque value for motor 1 required to slow down the gate.
Motor 1 slowing down torque setting between 1% and 99%.
Motor 2 slowing down
torque
(R2t SLoW)
45 %
Setting the torque value for motor 2 required to slow down the gate.
Motor 2 slowing down torque setting between 1% and 99%.
Opening time delay
(oPEn dELAY t IME)
1 s
Delay in starting motor 1 opening compared with motor 2, adjustable from 1 to 10 s.
Closing time delay
(cLS dELAY t IME)
1 s
Delay in starting motor 2 closing compared with motor 1, adjustable from 1 to 25 s.
Motor 1 fast travel time
(R1 FAST t IME)
15 s
Time spent at normal speed by motor 1 (not slowed), adjustable from 1 to 30 s.
Motor 2 fast travel time
(R2 FAST t IME)
15 s
Time spent at normal speed by motor 2 (not slowed), adjustable from 1 to 30 s.
Note:
The slow down time (during opening and closing) is obtained by timing the duration of an operation and entering a lesser value
in the "Motor fast travel time" parameter setting. If for example an operation lasts for 25 s, by entering a value of 20 s, we will obtain a
slow down time of 5 s.
Slow down speed
(SLow SPEEd)
50 %
Slow down speed reduction (from 0% to 99%) in relation to normal speed. A 0 value
corresponds to disabling the slow down function.