05
Installation & Operating Instructions
Installation Requirements
Before commencing installation of the unit
consideration should be given to the following:
1. Read these instructions thoroughly.
2. Chamber/opening dimensions.
MIN 420mm(W)x570mm(H)x75mm(D)
MAX440mm(W)x580mm(H)xNO MAX DEPTH
3. Open chimney/flue must be blocked off to
prevent downdrafts and chimney draw.
4. You will need the suitable tools.
5. You will need the suitable wall plugs for the
stability system eyelet.
6. Select a location that is not prone to moisture.
7. A 13 amp, 240 Volt socket capable of
accommodating a maximum load of 2050
watts must be available close to the
appliance. The socket must be accessible at
all times and must not be placed directly
behind the unit.
DO NOT INSTALL THE APPLIANCE
DIRECTLY ON CARPET OR SIMILIAR
SURFACES WHICH MAY RESTRICT
AIR CIRCULATION.
Unpacking & Testing
Carefully remove the unit from the packaging
and prior to installing the unit, test the unit by
plugging the power supply into a conventiently
located 13 amp earthed socket and run
through the controls. Your appliance is supplied
with the following items:
• Remote Control (2xAAA Batteries included)
4
INSTALLATION & OPERATING INSTRUCTIONS
INSTALLATION REQUIREMENTS
Before commencing installation of the unit consider-
ation should be given to the following:
1.
Read these instructions in conjunction with the
instructions which came with the appliance itself.
2.
Chamber/opening dimensions.
MIN 420mmWx570mmHx75mmD
MAX440mmWx580mmHxNO MAX DEPTH
3.
Open chimney/flue must be blocked off to
prevent downdrafts..
4.
You will need the tools of the trade.
6.
Select a location that is not prone to
moisture.
7.
A 13 amp, 240 Volt socket capable of
accomodating a maximum load of 2050
watts must be available close to the
appliance. The socket must be accessible at
all times and must not be placed directly
behind the unit.
DO NOT INSTALL THE APPLIANCE DIRECTLY
ON CARPET OR SIMILIAR SURFACES WHICH
MAY RESTRICT AIR CIRCULATION.
UNPACKING & TESTING
Carefully remove the unit from the packaging and
prior to installing the unit, test the unit by plugging
the power supply into a conventiently located 13
amp grounded socket.
Your Appliance is supplied with the following items:
•
Remote Control (2xAAA Batteries included)
Second Canop
y
The Fireplace is designed to fit with various frames
supplied by Capital. The second Canopy is assembled
onto the product as default seeting from factory.
Pls. follow the steps below to remove the second Canopy.
1. Removing 2pcs white screws on each side panels
with a screw driver (Fig. 2);
2. Pulling the Canopy out after screws are removed;
(Fig. 2);
3. The Fireplace with just Primary Canopy as shown
(Fig. 3)
Primary Canopy
NOTE:
For the Fireplace is fit with or without Second
Canopy Pls. refer to Frames Insatllation.
5.
You will need the suitable wall plugs for the
stability system eyelet.
1
2
3
4
5
6
Trim
without
canopy
Fit fire with
secondary
canopy
(already fitted
to fire)
Cast iron
frame
with
canopy
Fit fire with
secondary
canopy
removed
Installation Preparation
Before installing the SLE40, determine
which frame is to be fitted. (Fig.1 & Fig.3)
IMPORTANT - Removing Second
Canopy
The Fireplace is designed to fit with various
frames supplied by Capital. The SLE40i
comes supplied with the second canopy
fitted. Please follow the steps below to
remove the second Canopy when using
the cast iron fire frames with the SLE40i.
1. Remove 2 bright steel screws on each
side of the fire with a screw driver (Fig. 2);
2. Pull the Canopy forward after screws are
removed; (Fig. 2);
3. The SLE40i with just Primary Canopy is
shown in Fig. 3
4
INSTALLATION & OPERATING INSTRUCTIONS
INSTALLATION REQUIREMENTS
Before commencing installation of the unit consider-
ation should be given to the following:
1.
Read these instructions in conjunction with the
instructions which came with the appliance itself.
2.
Chamber/opening dimensions.
MIN 420mmWx570mmHx75mmD
MAX440mmWx580mmHxNO MAX DEPTH
3.
Open chimney/flue must be blocked off to
prevent downdrafts..
4.
You will need the tools of the trade.
6.
Select a location that is not prone to
moisture.
7.
A 13 amp, 240 Volt socket capable of
accomodating a maximum load of 2050
watts must be available close to the
appliance. The socket must be accessible at
all times and must not be placed directly
behind the unit.
DO NOT INSTALL THE APPLIANCE DIRECTLY
ON CARPET OR SIMILIAR SURFACES WHICH
MAY RESTRICT AIR CIRCULATION.
UNPACKING & TESTING
Carefully remove the unit from the packaging and
prior to installing the unit, test the unit by plugging
the power supply into a conventiently located 13
amp grounded socket.
Your Appliance is supplied with the following items:
•
Remote Control (2xAAA Batteries included)
Second Canop
y
The Fireplace is designed to fit with various frames
supplied by Capital. The second Canopy is assembled
onto the product as default seeting from factory.
Pls. follow the steps below to remove the second Canopy.
1. Removing 2pcs white screws on each side panels
with a screw driver (Fig. 2);
2. Pulling the Canopy out after screws are removed;
(Fig. 2);
3. The Fireplace with just Primary Canopy as shown
(Fig. 3)
Primary Canopy
NOTE:
For the Fireplace is fit with or without Second
Canopy Pls. refer to Frames Insatllation.
5.
You will need the suitable wall plugs for the
stability system eyelet.
4
INSTALLATION & OPERATING INSTRUCTIONS
INSTALLATION REQUIREMENTS
Before commencing installation of the unit consider-
ation should be given to the following:
1.
Read these instructions in conjunction with the
instructions which came with the appliance itself.
2.
Chamber/opening dimensions.
MIN 420mmWx570mmHx75mmD
MAX440mmWx580mmHxNO MAX DEPTH
3.
Open chimney/flue must be blocked off to
prevent downdrafts..
4.
You will need the tools of the trade.
6.
Select a location that is not prone to
moisture.
7.
A 13 amp, 240 Volt socket capable of
accomodating a maximum load of 2050
watts must be available close to the
appliance. The socket must be accessible at
all times and must not be placed directly
behind the unit.
DO NOT INSTALL THE APPLIANCE DIRECTLY
ON CARPET OR SIMILIAR SURFACES WHICH
MAY RESTRICT AIR CIRCULATION.
UNPACKING & TESTING
Carefully remove the unit from the packaging and
prior to installing the unit, test the unit by plugging
the power supply into a conventiently located 13
amp grounded socket.
Your Appliance is supplied with the following items:
•
Remote Control (2xAAA Batteries included)
Second Canop
y
The Fireplace is designed to fit with various frames
supplied by Capital. The second Canopy is assembled
onto the product as default seeting from factory.
Pls. follow the steps below to remove the second Canopy.
1. Removing 2pcs white screws on each side panels
with a screw driver (Fig. 2);
2. Pulling the Canopy out after screws are removed;
(Fig. 2);
3. The Fireplace with just Primary Canopy as shown
(Fig. 3)
Primary Canopy
NOTE:
For the Fireplace is fit with or without Second
Canopy Pls. refer to Frames Insatllation.
5.
You will need the suitable wall plugs for the
stability system eyelet.
Fig.1
Fig.2
Fig.3
Summary of Contents for SLE40i
Page 19: ...Wiring Diagram 19...