The active power limit can
be set on “AiSWEI cloud” application,
the details can be found in the user manual for the AISWEI Cloud
APP.
6.4 Active power control via demand response enabling device
(DRED)
The inverter shall detect and initiate a response to all supported
demand response commands, demand response modes are
described as follows:
Mode Requirement
DRM
0
Operate the disconnection device
DRM
1
Do not consume power
DRM
2
Do not consume at more than 50% of rated power
DRM
3
Do not consume at more than 75% of rated power
AND Source reactive power if capable
DRM
4
Increase power consumption (subject to constraints
from other active DRMs)
DRM
5
Do not generate power
DRMs application description
• Only applicable to AS/NZS4777.2:2015.
• DRM0, DRM5, DRM6, DRM7, DRM8 are available.