User Manual UM0025_ASW3000-6000H-S2_EN_V02_0722 51
The inverter shall detect and initiate a response to all supported
demand response commands , demand response modes are
described as follows:
Mode
Requirement
DRM 0 Operate the disconnection device
The RJ45 socket pin assignments for demand response modes
as follows:
Pin1-------- DRM 1/5
Pin2------- DRM 2/6
Pin3------- DRM 3/7
Pin4------- DRM 4/8
Pin5------- RefGen
Pin6------- Com/DRM0
Pin7--------N/A
Pin8------- N/A
7.3 Earth Fault Alarm
This inverter complies with IEC 62109-2 clause 13.9 for earth
fault alarm monitoring. If an Earth Fault Alarm occurs, the red
color LED indicator will light up. At the same time, the error code
38 will be sent to the AISWEI Cloud.
(This function is only available in Australia and New Zealand)