36 User Manual UM0025_ASW3000-6000H-S2_EN_V02_0722
2. Loosen the swivel nut of AC connector. Insert the crimped
conductors into corresponding terminals and tighten screws
with the accompanied wrench tool (Torque: 1.4Nm). Insert the
adapter to the socket element, stuff the sealing sleeve into the
adapter and tighten the swivel nut.
3. Plug the AC connector into the socket for the EPS connection.
Object
Description
Value
A
External diameter
10-16mm
B
Copper conductor cross-section
2.5-6mm
2
C
Stripping length of the insulated
conductors
13mm
D
Stripping length of the cable
outer sheath
53mm
The PE conductor must be 2 mm longer than the L and N
conductors.