SIG-5600 User Manual Ver. 1.0
- 32 -
5
Register Map
5.1
Read Only
5.1.1
Analog Input Value Register
This register is for storing the most recently stored analog input value. The
range of values is 0 to 4095.
Division
Address
Word Count
Type
Function Code
HMI Addressing
Example
Port 0
0
1
Integer
04
30001
Port 1
1
1
Integer
04
30002
Port 2
2
1
Integer
04
30003
Port 3
3
1
Integer
04
30004
Table 5-1 Analog Input Value Register
5.1.2
Minimum Analog Input Value Register
This register is for storing the minimum value among analog input values. The
range of values is 0 to 4905.
Division
Address
Word Count
Type
Function Code
HMI Addressing
Example
Port 0
16
1
Integer
04
30017
Port 1
17
1
Integer
04
30018
Port 2
18
1
Integer
04
30019
Port 3
19
1
Integer
04
30020
Table 5-2 Minimum Analog Input Value Register
5.1.3
Maximum Analog Input Value Register
This register is for storing the maximum value among analog input values. The
range of values is 0 to 4905.
Division
Address
Word Count
Type
Function Code
HMI Addressing
Example
Port 0
32
1
Integer
04
30033
Port 1
33
1
Integer
04
30034
Port 2
34
1
Integer
04
30035
Port 3
35
1
Integer
04
30036
Table 5-3 Maximum Analog Input Value Register
The minimum and maximum values of analog input can be initialized using the Reset
Analog Input Min/Max Value Register.