3.3 Fixed PF
Description: This mode is to set a fixed power factor output
Range: -0.8~+0.8
Default: 1
3.4 Reac-Power
Description: This mode is to set a fixed reactive power output
Range:-60%~+60%
Default: 0%
3.5 Power-PF
Description: This mode is not required in Australia.
10.5.2 Power Rate Limit
To set the power rate limits for increase and decrease in power level per minute.
Wgra+: 5-100%, Default:16%
Wgra-: 5-100%, Default:16%
10
.
5
.
3 Freq Derate Set
To set the frequency response limits for response to a decrease/increase in frequency.
10
.
5
.
4 10mins Voltage Set
To set the 10mins average protection limit.
Range: 244V to 258V
Default: 4777-A (258V); 4777-B(258V); 4777-C(258V); 4777-N(249V)
10
.
5
.
5 DRM Settings
“DRM ON/OFF” is used to enabled or disable the functionality of the DRM port.
“DRM3” and “DRM7” are used to define the reactive power absorption for DRM3 and
DRM7
.
Range: 0~- 60%
OVF_Start(F_ULCO):
50.1Hz~50.5Hz
(Default: 4777-A(50.25Hz), 4777-B(50.15Hz), 4777-C(50.5Hz), 4777-N(50.2Hz))
OVF_Stop(F_Pmin):
51Hz~53Hz
(Default: 4777-A(52Hz), 4777-B(52Hz), 4777-C(53Hz), 4777-N(52Hz))
UNF_Start(F_LLCO):
49.5Hz~49.9Hz
(Default: 4777-A(49.75Hz), 4777-B(49.85Hz), 4777-C(49.5Hz), 4777-N(49.8Hz))
UNF_Stop(F_Pmax):
47Hz~49Hz
(Default: 4777-A(48Hz), 4777-B(48Hz), 4777-C(47Hz), 4777-N(48Hz))
.82.
10. Appendix
10. Appendix
.83.
Model
GHX5-32P
PV category
Ue
Ie
Ui
Uimp
Icw
Icm
I(make)/Ic(break)
Complied standard
DC-PV2
1100V
1500V
8000V
700A
1400A
120A
AS 60947.3
DC switch brand
Beijing People
30A
10.6 Built-In DC Isolator Specification
A DC-PV2 switch , complied to AS60947.3:2018 ,within the inverter, is used as isolating
device. Please check below ratings.