8.2.5 Fan motor unit
Motor and bearing are maintenance-free.
If necessary, clean the impeller with a soapy solution.
Check that the test lead (if fitted) is seated firmly at the test
connector on the inlet nozzle.
Loose seating can result in faulty measurements.
The integral installation aid facilitates removal of the complete
fan/motor unit with front plate.
8.2.6 Filter pre-dryer (accessories)/reheater (accessories)
>>
Check and clean at regular intervals.
>>
Check whether the manually resettable high limit safety cut-out responds.
>>
Reset the high limit safety cut-out by pressing the reset button.
>>
Cleaning the electric coils:
•
Vacuum, taking care not to bend the indirect coils
•
Blast with compressed air, max. 1 bar
>>
If the cleaning pressure is too high, there is a risk of irreparable mechanical damage to the electric coils.
>>
The electric coils must be protected from moisture and water.
8.2.7 Bypass damper/extract air damper/outdoor air damper
>>
Check the dampers for ease of movement.
>>
Never lubricate the dampers.This could destroy the plastic used and
compromise the damper function.
>>
To clean, wipe down with a soapy solution; otherwise maintenance-free.
8.2.8 Compact filter
•
The compact filters cannot be regenerated.
•
They must be replaced when they are dirty, or no later than after 12 months.
•
The compact filters can be removed from the unit casing once the inspection
doors have been opened (see spare parts).
>>
Never operate the CPL-C ventilation unit without filters.