7
InstallatIon and oPERatIon ManUal FoR sl2 solaR ModUlEs oF tHE GEnERatIon G2.1 and G2.2
2 plannIng
requirements on the clamping system for framed modules
When using framed Solibro products, it is important to ensure that
there is no potential difference between frame and ground. There
are two options available for this:
option 1:
usage of grounding clamps with grounding function
specifiedintheapprovedSolibroclampslist.Onrequest,Solibro
can test clamp systems and approve them following successful
testing.
option 2:
Potential equalization of the module must be done via
one of the grounding holes on the module frame. in that case,
usageofclampswithoutgroundingfunctionisvalidiftheyfulfil
the following requirements:
clamp height corresponding to 30 mm frame height.
clamp depth: 7–12 mm.
Clampswhichfulfilthestaticrequirementsofthelocation.
Clampswithlong-termstability,whichfixthemodulesecurely
on the mounting frame.
clamps do not deform the frame.
Minimumwidthmiddleclamp:≥40mm
Minimumwidthendclamp:≥40mm
¼
See applicable documents “List of approved clamps and
mounting systems”
¼
See also information on potential equalization in chap. 5.2
Fig. 4
clamping of framed modules
7–12
clamp
Glass (module top side)
clamp depth
Glass (module bottom side)
Module frame
Active surface
Frame tape
All measurements in mm.