Brake Selection

 

 
 

General

 

 
The Solbrake / SMB - Solid State Motor Brake provides 
fast, smooth, frictionless braking of three-phase 
squirrel-cage motors by injecting controlled DC current to 
the motor windings, after Mains contactor opened. This 
induces a stationary magnetic field, which exerts a braking 
torque on the rotor. 

 

Stopping time can be similar to the time it takes to reach 
full speed on a Direct-On-Line starting. 

 

Adjustable Braking Torque and Braking Time enable 
perfect matching of the brake to the driven load. 

 

Automatic sensing System turns the brake off 
automatically when the motor comes to a full stop.  This 
minimizes the motor heating. 
 
 
 
 
 
 
 
 
 
 
 
 

Brakes ratings and Frame sizes 

Max Motor 

FLA (Amp) 

Brake Type 

FLC 

Frame 

Size 

 

Case 

material 

 

10 Solbrake 

10 

SB0 

PC/ABS 

17 Solbrake 

17 

31 Solbrake 

31 

58 Solbrake 

58 

SB1 

 

Aluminum 

105 Solbrake 

105 

170 Solbrake 

170 

210 Solbrake 

210 

SB2 

310 Solbrake 

310 

390 Solbrake 

390 

SB3 

 
 

Metal 

 

 

 
Dimensions (mm) 

Size 

Width 

Height 

Depth 

SB0 45 75 105 
SB1 65 190 114 
SB2 154 280 160 
SB3 224 384 222 

 

Select the brake according to the following criteria: 

 
M

 

otor Current & starting conditions

 

• 

Motor's Full Load Ampere (FLA) - as indicated 
on its nameplate (even if the motor is not fully 
loaded).  

 

 

• 

The Solbrake (SMB) is designed for a duty cycle 

f 10% or less; e.g. 10 sec. operation, 90 sec. rest. 

o

 

Duty Cycle - the ratio between operating time 
and  
total cycle time (rest time + Braking time). 

 

                                  Braking time 

Duty Cycle =  ------------------------------- x 100 (%) 

                               Rest time + Braking time 
 

Note

If a higher duty cycle is required select a higher Solbrake 
(SMB) type to allow enough brake time current. 

 

Centrifuge

RPM 

Stopping Time 

t

SMB 

Wood Saw 

 

Mains Voltage (line to line)

 

Thyristor's PIV rating, internal circuitry and insulation 
determines six voltage levels: Each brake is factory set 
for one of the following levels according to the Ordering 
Information. 

Voltage 

Tolerance 

220- 240 V  

+10  -15 % 

380 - 415 V 

+10  -15 % 

440 V 

+10  -15 % 

460 - 500 V 

+10  -15 % 

575 - 600 V 

+10  -15 % 

690 V (210A-390A) 

+10  -15 % 

 

Each brake is factory set for one of the above levels and 
suitable for 50 or for 60 Hz (

±

 5%). 

 

Options

 (see Ordering Information) 

For extended braking time 

consult factory and provide the 

following information: 

• 

Ambient temperature. 

• 

Actual stopping current. 

• 

Actual stopping time. 

• 

Time interval between starts

 

• 

Load characteristics

 

 

 

 

Summary of Contents for Solbrake

Page 1: ...Solbrake SMB Electronic Motor Brake DC Injection 8 390A 220 690V I In ns st tr ru uc ct ti io on n M Ma an nu ua al l Ver 11 0 11 2002 1...

Page 2: ...ction IP00 ATTENTION 1 This product was designed and tested for compliance with IEC947 4 2 for class A equipment 2 The Solbrake SMB brakes are designed to meet UL requirements 3 Use of the product in...

Page 3: ...ect the brake according to the following criteria Motor Current starting conditions Motor s Full Load Ampere FLA as indicated on its nameplate even if the motor is not fully loaded The Solbrake SMB is...

Page 4: ...tected against short circuit by fast acting fuses Recommended I2 t values in page 9 Transient Protection Line transient voltages can cause malfunctioning of the brake and damage to the SCRs When high...

Page 5: ...commended to apply some minimal inertia on the motor shaft The Solbrake SMB incorporates the following built in time delays t1 DC Injection Brake Contactor Motor Contactor 1 2 Open t2 t3 t4 t5 1 2 Clo...

Page 6: ...ls L1 and L2 internal contact Ca in Solbrake SMB controlling motor contactor closes after Mains voltage is connected and terminal 1 2 are open When operating in Manual mode DC injection will stop afte...

Page 7: ...L C1 C2 SMB Control M L1 L2 U V W C2 O L 1 2 SMB Power 3 4 5 6 Ca Cb C2 1 Cr 2 Stop O L Cf C2 SMB Control Start Forward Cf 2 Cr 1 Cf 1 Cr 3 Cf 4 Cr Start Reverse Cf 3 Cr 4 Cf Cr Reversing C2 SMB Cont...

Page 8: ...g has ceased and motor is still turning increase braking Torque setting and try again b If motor has stopped and the Yellow LED remains on decrease Braking Time setting until the Yellow LED turns off...

Page 9: ...C 000 BS 88 180 C330144 H600399 Solbrake SMB 105 100000 GSGB350 500V 350A 6 6 URD 2x000 BS 88 355 V330160 H600399 Solbrake SMB 210 600000 GSGB580 500V 710A 6 6 URD 31 D 11 0630 Q300026 D600188 Solbrak...

Page 10: ...Technical Specification Solbrake 17A 105 90 105 75 6 5 4 3 2 1 L2 L1 W V U Solbrake 31 58A 10...

Page 11: ...Technical Specification Solbrake 105 210A 77 12 20 17 12 12 M6 W L1 L2 U V 280 263 160 Solbrake 310 390A V 63 4 L W V 222 224 W L 384 18 18 L U U L 11...

Page 12: ...2 10 sec Optionally 1 30 sec Protection Automatic stopped motor sensor Switches off the DC injection automatically when motor has come to a complete stop Indications ON Green Illuminates when power is...