Wiring &  Operation

 

 

Solbrake / SMB with Direct on Line Starter

 

 

Motor contactor 

C

1

 (with one N.O + two N.C contacts). 

* Contact 

C

1-3

 - Holding N.O contact of contactor 

C

1

 

* Contact

 C

1-1

 - auxiliary N.C contact of contactor 

C

1

,  

  initiates the braking process. 
* Contact

 C

1-2

 - auxiliary N.C contact of motor contactor 

acts as an interlock preventing operation of brake 
contactor as long as motor contactor is closed. 

Brake contactor  

C

  2

 

(with one N.C contacts). 

* Contact

 C

2-1

 - auxiliary N.C contact of contactor C

2

    acts as an interlock preventing operation of motor 
    contactor as long as brake contactor is closed.

 

Note:  

There is electro mechanical interlock between C

1

 and C

2

.

 

Solbrake / SMB contacts

 

* Ca

 contact (Solbrake / SMB terminals 3-4 ), contact 

closes when Mains voltage is connected to Solbrake / 
SMB terminals and terminal 1-2 are open. 

Cb

 contact  (Solbrake / SMB terminals 5-6), closes upon 

stop signal and contact terminals 1-2 closes after time 
delay t

1

Notes

  

* Motor contactor C

1

 cannot be operated when Mains 

voltage is not connected to terminals L

1

 and L

(internal 

contact Ca in Solbrake / SMB, controlling motor 
contactor, closes after Mains voltage is connected and 
terminal 1-2 are open. 

*  When operating in Manual mode, DC injection will stop 

after time delay t

3

 as set on the Braking Time 

potentiometer. 

 

 

 

Operation 

Upon start signal, as 

Ca

 is closed, motor contactor C

1

 

closes, motor will operate and contact C

1-1

 opens. 

Upon stop signal, motor contactor C

1

 opens, contact C

1-1

 

closes and initiates the braking process. 

Contact Ca opens, preventing motor contactor operation, 
and after time delay t1 contact C

b

 closes, closing the brake 

contactor C

2

The yellow LED on Solbrake / SMB's front panel will light 
up indicating that brake contactor is closed. 

After time delay of approx. 0.05 sec. DC current will be 
injected to motors' winding. 

The yellow LED on Solbrake / SMB's front panel will light 
up indicating that braking current is now injected to the 
motor.  

The DC injection will automatically cease when motor 
comes to a complete stop (when Automatic mode is 
selected) and the yellow LED turns off. 

Contact Ca closes after time delay t

5

, permitting motor 

restarting.

 

 

 
 

 

 

 

M

 

L

 

1

 

L

 

2

 

U V  W 

1

 

2

 

O/L 

1

 

2

 

1-1

 

SMB 

Power 

3

 

4

 

5

 

6

 

a

 

b

 

2-1

 

1-2

 

1

 

Start 

Stop 

O/L 

1

 

2

 

SMB 

Control 

Summary of Contents for Solbrake

Page 1: ...Solbrake SMB Electronic Motor Brake DC Injection 8 390A 220 690V I In ns st tr ru uc ct ti io on n M Ma an nu ua al l Ver 11 0 11 2002 1...

Page 2: ...ction IP00 ATTENTION 1 This product was designed and tested for compliance with IEC947 4 2 for class A equipment 2 The Solbrake SMB brakes are designed to meet UL requirements 3 Use of the product in...

Page 3: ...ect the brake according to the following criteria Motor Current starting conditions Motor s Full Load Ampere FLA as indicated on its nameplate even if the motor is not fully loaded The Solbrake SMB is...

Page 4: ...tected against short circuit by fast acting fuses Recommended I2 t values in page 9 Transient Protection Line transient voltages can cause malfunctioning of the brake and damage to the SCRs When high...

Page 5: ...commended to apply some minimal inertia on the motor shaft The Solbrake SMB incorporates the following built in time delays t1 DC Injection Brake Contactor Motor Contactor 1 2 Open t2 t3 t4 t5 1 2 Clo...

Page 6: ...ls L1 and L2 internal contact Ca in Solbrake SMB controlling motor contactor closes after Mains voltage is connected and terminal 1 2 are open When operating in Manual mode DC injection will stop afte...

Page 7: ...L C1 C2 SMB Control M L1 L2 U V W C2 O L 1 2 SMB Power 3 4 5 6 Ca Cb C2 1 Cr 2 Stop O L Cf C2 SMB Control Start Forward Cf 2 Cr 1 Cf 1 Cr 3 Cf 4 Cr Start Reverse Cf 3 Cr 4 Cf Cr Reversing C2 SMB Cont...

Page 8: ...g has ceased and motor is still turning increase braking Torque setting and try again b If motor has stopped and the Yellow LED remains on decrease Braking Time setting until the Yellow LED turns off...

Page 9: ...C 000 BS 88 180 C330144 H600399 Solbrake SMB 105 100000 GSGB350 500V 350A 6 6 URD 2x000 BS 88 355 V330160 H600399 Solbrake SMB 210 600000 GSGB580 500V 710A 6 6 URD 31 D 11 0630 Q300026 D600188 Solbrak...

Page 10: ...Technical Specification Solbrake 17A 105 90 105 75 6 5 4 3 2 1 L2 L1 W V U Solbrake 31 58A 10...

Page 11: ...Technical Specification Solbrake 105 210A 77 12 20 17 12 12 M6 W L1 L2 U V 280 263 160 Solbrake 310 390A V 63 4 L W V 222 224 W L 384 18 18 L U U L 11...

Page 12: ...2 10 sec Optionally 1 30 sec Protection Automatic stopped motor sensor Switches off the DC injection automatically when motor has come to a complete stop Indications ON Green Illuminates when power is...

Reviews: