2.2 Important Safety Instructions

Danger!
Danger to life due to high voltages in the inverter!

All work  must be carried out by qualified electrician.
The appliance is not to be used by children or persons with                  
reduced physical sensory or mental capabilities, or lack of 
experience and knowledge, unless they have been given 
supervision or instruction.
Children should be supervised to ensure that they do not play 
with the appliance.

Caution

!

Possible  damage  to  health  as  a  result  of  the  effects  of 
radiation!

Do not stay closer than 20 cm to the inverter for a long time.

Note

!

Grounding the PV generator. 

Comply with the local requirements for grounding the PV
modules and the PV generator. SolaX recommends connecting 
the generator frame and other electrically conductive surfaces 
in  a  manner  which  ensures  continuous  conduction  and 
ground  these  in  order  to  have  optimal  protection  of  system 
and persons.

Warning

!

Ensure  input  DC  voltage  ≤Max.  DC  voltage.  Over  voltage 
may  cause  permanent  damage  to  inverter  or  other  losses, 
which will not be included in warranty! 

 

Warning

!

Authorized  service  personnel  must  disconnect  both  AC  and 
DC  power  from  X3-PRO  G2  series  before  attempting  any 
maintenance or cleaning or working on any circuits connected 
to the X3-PRO G2 series.

Prior  to  the  application,  please  read  this  section  carefully  to  ensure  correct 
and safe application. Please keep the user manual properly.
Use only attachments recommended or sold by SolaX. Otherwise may result 
in a risk of fire, electric shock, or injury to person.
Make  sure  that  existing  wiring  is  in  good  condition  and  that  wire  is  not 
undersized. 
Do  not  disassemble  any  parts  of  inverter  which  are  not  mentioned  in 
installation  guide.  It  contains  no  user-serviceable  parts.  See  Warranty  for 
instructions  on  obtaining  service.  Attempting  to  service  the  X3-PRO  G2 
Series  inverter  yourself  may  result  in  a  risk  of  electric  shock  or  fire  and  will 
void your warranty. 
Keep away from flammable, explosive materials to avoid fire disaster.
The installation place should be away from humid or corrosive substance.
Authorized  service  personnel  must  use  insulated  tools  when  installing  or 
working with this equipment.
PV modules shall have an IEC 61730 class A rating.
Never touch either the positive or negative pole of PV connecting device.

 Strictly 

prohibit touching both of them at the same time.

 

The unit contains capacitors that remain charged to a potentially lethal voltage
after the MAINS and PV supply have been disconnected.
Hazardous voltage will present for up to 5 minutes after disconnection from 
power supply.
CAUTION - RISK of electric shock from energy stored in capacitor. Never operate 
on the solar inverter couplers,  The MAINS cables, PV cables or the PV generator 
when power is applied. After switching off the PV  and Mains, always wait for 5 
minutes to let the intermediate circuit capacitors discharge before you unplug 
DC and MAINS couplers.
When accessing  the internal circuit of solar inverter, it is very important to wait 5 
minutes before operating the  power circuit or demounting the electrolyte 
capacitors inside the device. Do not open the device before hand since the 
capacitors

time to sufficiently discharge!

 require 

Measure the voltage between terminals UDC+ and UDC- with a multi-meter 
(impedance at least 1Mohm) to ensure that the device is discharged before
beginning work (35VDC) inside the device.

             

            

Safety

Safety

07

06

Do not operate the  inverter when the device is running.

Risk of electric shock!

Caution

!

Danger of burn injuries due to hot enclosure parts!

During operation, the upper lid of the enclosure and the 
enclosure body may become hot.
If necessary, touch the lower temperature

 

enclosure lid during 

operation.

Warning

!

Warning

!

Summary of Contents for X3-PRO G2 Series

Page 1: ...on or individual should not plagiarize partially or fully copy including software etc and no reproduction or distribution of it in any form or by any means shall be allowed All rights reserved SolaX P...

Page 2: ...Inverter 3 3 Dimension 4 Technical Data 4 1 DC Input 4 2 AC Output 4 3 Efficiency Safety and Protection 4 4 General Data 5 Installation 5 1 Check for Transport Damage 5 2 Packing List 5 3 Installatio...

Page 3: ...ation appear in this document as described below 1 Notes on this Manual 7 Troubleshooting 7 1 Trouble Shooting 7 2 Routine Maintenance 8 Decommissioning 8 1 Dismantling the Inverter 8 2 Packaging 8 3...

Page 4: ...rator if the voltage protection level VP of the surge arresters is greater than 1100V an additional SPD type 3 required surge protection for electrical devices 05 04 Safety Safety Anti Islanding Effec...

Page 5: ...nstructions on obtaining service Attempting to service the X3 PRO G2 Series inverter yourself may result in a risk of electric shock or fire and will void your warranty Keep away from flammable explos...

Page 6: ...irements of BS 7671 Electrical installation of PV system shall comply with requirements of BS 7671 and IEC 60364 7 712 No protection settings can be altered User shall ensure that equipment is so inst...

Page 7: ...ulations Compliance with safety regulations depends upon installing and configuring system correctly including using the specified wires The system must be installed only by professional assemblers wh...

Page 8: ...RS485 AC connector Pocket WiFi LAN optional 4G optional 482 00 mm 417 00 mm 186 00 mm 417 00 mm X3 PRO 12K G2 2D Ground connection port G 25500 1100 650 160 980 400 850 32 32 40 40 200 2 A 2 B 2 X3 P...

Page 9: ...K G2 2D X3 PRO 10K G2 2D X3 PRO 15K G2 2D X3 PRO 12K G2 2D 99 90 97 80 98 30 X3 PRO 25K G2 3D X3 PRO 30K G2 3D 99 90 98 00 98 50 14 15 99 90 97 80 98 30 99 90 97 80 98 30 Technical Data Technical Data...

Page 10: ...onal 1 M N PV pin contact positive 4 negative 4 for two strings positive 6 negative 6 for three strings Terminal block 1 RJ45 connector 1 F F 4 1 X3 PRO 8K G2 2D X3 PRO 10K G2 2D X3 PRO 15K G2 2D X3 P...

Page 11: ...thin 5 5 4 Installation Steps Preparation Below tools are needed before installation Installation Installation The wall hanging the inverter should meet conditions below 1 solid brick concrete or stre...

Page 12: ...eat dissipation The distance of installation space for multiple inverters is as follows Step 1 Fix the bracket to the wall First find the expansion screws and the bracket in the accessory bag as shown...

Page 13: ...agon wrench to tighten them c Expansion bolts Rubber hammer d Self tapping screw Outer hexagonal wrench Gasket Step 3 Tighten the inverter and bracket f Use the inner hexagonal wrench to tighten the i...

Page 14: ...Main Steps to Connect to the Inverter Inverter BMU Installation Installation Model Danger Danger to life due to high voltage on DC conductors when exposed to sunlight the PV array generates dangerous...

Page 15: ...h indicates that the connection is completed Step 6 Tighten the fastening head and insert into the corresponding positive and negative PV PV ports of the inverter Step 4 Tighten the PV pin contact and...

Page 16: ...5 6 mm 8 10 mm c Fetch the AC waterproof cover from the carton e Strip 82 mm of insulation from the cable ends by using the stripping pliers Micro breaker 16 A 32 A 50 A 2 5 5 mm 3 6 mm 3 6 mm 3 6 mm...

Page 17: ...operating time of the fuses is less than 5 seconds installation method B2 according to 60204 1 2006 annex D cable in conduit EN cable trunking system number of loaded circuit only one Use H07 cord RN...

Page 18: ...ebsite via connecting Pocket WiFi Pocket LAN can be purchased from the supplier for optional if needed Connection steps Please check the Pocket WiFi user manual for more details This is a communicatio...

Page 19: ...Pin Definition 1 2 3 4 5 6 7 8 X X Heat Pump Controller X X X X b Dry Contact is provided to control the closing and breaking of switches by giving control signals as below c Heat Pump Controller is...

Page 20: ...disconnected with grid If the Pocket WiFi is connected to the port please remove the Pocket WiFi at first 3 Then insert the U disk into the Dongle port on the bottom of the inverter Then turn on DC sw...

Page 21: ...er starting up successfully Waiting Inverter is waiting to checking when DC input voltage from panels is greater than 160 V lowest start up voltage but less than 200 V lowest operating voltage Checkin...

Page 22: ...n 2021 01 01 00 00 Enter Back U1 0 0V Down Up errors were kept English German XXXXXXXXXXXXXX User can see the U I F of the grid Ua Ia Fa Ub Ib Fb Uc Ic Fc Pout Pgrid Export Control DRM Function Grid S...

Page 23: ...V Stage3 287 5 103 5 103 5 P freq Back Back Enter Up Down Enter Back Proportion x xx Up Down Grid Protection Enter Back Enable Freq ROCOF T_Start Up Down Up Down Up Down 60s H LVRT Function Disable U...

Page 24: ...interface Level 1 is the default interface the inverter will automatically jump to this interface when the system started up successfully or not operated for a period of time The interface shows the...

Page 25: ...an UserDefined option which allows the user to customize relevant parameters within a wider range b Export Control With this function the inverter can control energy exported to the grid Whether havi...

Page 26: ...n in curve A For E 8001 curve cos f P should refer to curve B Default values of setting are as shown in curve B Reactive power control Reactive standard curve Q f V Q V Qmax Qmax V2s V1s V1i V2i V2i 0...

Page 27: ...aving factory according to safety rules If reset is needed any changes should be made according to the requirements of local grid h Mppt Scan Mode There are four modes to be selected off low freq scan...

Page 28: ...ent Dry Contact Load Management Disable Manual Smart Save Enter Back n PV Connection The user can select the PV connection type by this function Mode Select Mode Select Multi Comm o Nline Control The...

Page 29: ...age Out of Normal Range Check if the PV input voltage is within the operating range of the inverter Disconnect PV wiring and reconnect Or seek help from us 54 Faults Diagnosis and Solution GridVolt10M...

Page 30: ...n the rear of the inverter are covered by dirt and the machine should be cleaned and absorbed dust when necessary This work shall be performed from time to time 2 Check that if the indicators of the i...

Page 31: ...h as earthquake flooding thunderstorm lighting fire hazard volcanic eruption etc Inverter s warranty is expired and doesn t buy extended warranty Can t provide the inverter s SN warranty card or invoi...

Page 32: ...Module Brand Module Size W Number of String Number of Panel Per String Battery Type Brand Number of Battery Attached Battery If Any Module If Any Date of Delivery Signature Please visit our warranty w...

Page 33: ...YOUR INVERTER ONLINE WIN SOLAX POINTS Open your camera app and point your device at the QR code Wait for the camera to recognize the QR code Click banner or noti cation when it appears on the screen W...

Reviews: