46
47
Operation Method
Operation Method
* Password
The default password is “
2014
” for the installer, which only allows the installer
to review and modify necessary settings complying to the local rules and
regulations. If further advanced setting is required, please contact the
distributor or SolaX for assistance. We need to increase or decrease the word
by pressing up or down button. Press “Down” to confirm an alternate to the
next word. After word is confirmed, long press “Down” to enter password.
Ÿ
Settings
Setting function is used for setting the inverter for safety, connection, Grid
and so on.
Settings
Safety
Export Control
Password
0 0 0 0
Safety
country
VDE4105
When inputting the password, the information of the LCD interface is shown
as below.
a) Safety
The user can set the safety standard here according to different countries
and grid tied standards. There are several standards for choice (May change
without notice). In addition, the user has an “UserDefined” option which
allows the user to customize relevant parameters within a wider range.
﹦﹦﹦﹦
﹦﹦﹦﹦
﹦﹦﹦﹦
﹦﹦﹦﹦
﹦﹦﹦﹦
﹦﹦﹦﹦
b) Export Control
With this function the inverter can control energy exported to the grid.
Whether having this function is based on user’s wishes.
Choose ”Meter” in ”Meter/Disable” means user must install a meter to monitor
energy exported to the grid. There are user value and factory value. The
factory value is default which can not be changed by user. The user value set
by installer must be less than the factory value and within the range of 0 kW
to 30 kW.
Choose ”Disable” means the function will be shut off.
Press ”Up“ and “Down” button to select and long press ”Down” to confirm.
d)
Grid Services
Usually end user do not need to set the grid parameters. All default value have
been set before leaving factory according to safety rules.
If reset is needed, any changes should be made according to the requirements
of local grid.
Export Control
Mode Select
Meter/Disable
c) DRM Function
Installer can choose ”Enable” to control the inverter’s power off through the
external communication.
DRM Function
Grid Services
Mode Select
Enable/Disable
P(freq)
so
start
*
*
﹦﹦﹦
﹦﹦﹦
﹦﹦﹦
﹦﹦﹦
﹦﹦﹦
﹦﹦﹦