Operation
61
7.1 Start Inverter
7.2 Shut Down Inverter
Operation
NOTE!
If the left indicator do not turn green please check the below points:
- All the connections are correct.
- All the external breakers are switched on.
- The DC switch on the inverter is in the “ON” position.
7 Inverter Operation Procedures
7.3 Definition of indicator light
60
NOTE!
When error occurs, please check the status of Fault LED 1 and Fault
LED 2 indicator lights simultaneously.
Before you switch on the circuit breaker of battery, make sure that
the Battery ON/OFF button has been switched off. If the Battery
ON/OFF button is switched on, then you switch on the circuit
breaker of battery, the inverter and the battery may be damaged.
NOTE!
Switch on the PV DC switch of the inverter(turn to “ON”
position).
Make sure the
Battery ON/OFF button is
s
witch
ed
off.
Switch on the circuit breaker of battery.
Switch on the Battery ON/OFF button.
Switch on the
BI
ON/OFF button.
Switch on the AC circuit breakers for the
BI
and inverter.
Switch on the AC circuit breakers for the generator.
The system will start up. Check the status of indicators on inverter, battery and
BI
for more information on the codes displayed for error and warning messages, refer
to section
7.3.
Download and set the APP
.
If the system has been turned on,
p
ress the inverter power on button for 1
second to turn off the inverter.
Switch off the PV DC switch of the inverter(turn to
“
OFF
”
position
).
Switch off the Battery ON/OFF button.
Switch off the circuit breaker of battery.
Switch off the AC circuit breakers for the
BI
and inverter.
Switch off the AC circuit breakers for the generator.
Message Explanation
Red
GREEN
ON
ON
Other issue
ON
0.5s on, 0.5s off
Arc fault occurs
ON
2s on, 2s off
Ground fault occurs
OFF
0.5s on, 0.5s off
PV Voltage Fault
OFF
2s on, 2s off
Grid error
0.5s on, 0.5s off
0.5s on, 0.5s off
Firmware upgrading is ongoing
OFF
OFF
No errors
Fault LED
Color and Status
LED
Color
Status
Behavior
Message Explanation
Green
ON
Constant on
The inverter is in normal status or in backup mode
Green
OFF
Constant off
The inverter has a fault
Green
BLINK
1s on, 1s off
The inverter is in waiting or checking status
Green
ON
Constant on
The battery communication is normal and working
Green
BLINK
1s on, 1s off
The battery communication is normal and in idle status
Red
ON
Constant on
The battery does not communicate with inverter
Operation LED
BAT LED
Operation
LED
BAT
LED
Fault LED 1
Fault LED 2