![SolaX Power A1-AC-G2 Series Installation And Operation Manual Download Page 10](http://html1.mh-extra.com/html/solax-power/a1-ac-g2-series/a1-ac-g2-series_installation-and-operation-manual_1314282010.webp)
3.6 Internal Terminals in Wiring Box
NOTE!
Not all communication wirings connected with the terminals on the
communication board are shown in the picture.
Refer to the Section 6 for the details on communication connection.
3.7 Identification of
Series
A1-HYB-G2
A1-7.0-US
A1-6.0-US
076
AH2
E
7
0
0
1
Model Power
Year
Month Work Order Number
Serial Number
0
0
1
1. Every A1-G2 series product corresponds to a unique serial number. The series
serial number is divided into five parts: type (3 bits)+ power (3 bits)+ year/month (2
bits)+ work order number (3 bits)+ stream number (3 bits) a total of 14bits.
AH2: A1-HYB-G2; AA2:A1-AC-G2; AS2:A1-SMT-G2
076: Power ----7.6KW;
E: Year ------ D:2018 (A:2014; B: 2015......)
7: Month ------ July (October :A, November ;B, December......)
001: Work order number---- 001:001~999 (Monthly zero clearing)
001: Serial number---- 001:001~ZZZ (will be Cleared for next work order).
Introduction
Introduction
15
14
Model
Parameter
Serial Number Identification
Model: A1-HYB-3.8K-G2
No. of MPPT/Strings per MPPT
Operating Voltage range
Max.DC Current per MPPT
Max.DC Power
Nominal AC Voltage
Max. Continuous AC Power
Max. Continuous Current
Nominal AC Frequency
2/1
16 A
5700 W
60 Hz
0.8 Leading- 0.8 Lagging
90-500 Vd
.
c
.
AC Output Power Factor
GRID OUTPUT/ INPUT
15
.
9 A
3816 VA
PV INPUT
GRID SUPPORT UTILITY-INTERACTIVE
TRANSFORMERLESS INVERTER
120/240 Vac split phase
59.3 Hz-60.5 Hz
Operating Frequency Range
BATTERY
Battery Type
DC Operating Voltage Range
Max. Charge / Discharge Current
Li-ion
75-450Vd c
. .
54 A / 54 A
Nominal DC Voltage
150 Vd c
. .
Max.DC Voltage
550 Vd
.
c
.
615.00053.00
MADE
IN
CHINA
272687
DC Operating Voltage Range
Max. Charge / Discharge Current
75-450Vd c
. .
54 A / 54 A
OTHER
Enclosure Type
Type 4X
Inverter
SN:
SolaX Power Network Technology (Zhejiang) CO., LTD.
ADD:No
.
288
Shizhu Road,Tonglu Economic Development Zone,
TEL: +86 571 5626 0011 E-mail: [email protected]
Dongxing District,Tonglu City, Zhejiang Province, China.
Nominal DC Voltage
150 Vd c
. .
Operating Temperature
LISTED
UL. 1741 / UL 62109-1 / CSA107.1
-
13
˚
F~+140
˚
F
no derating below 113
˚
F
A
B
E
F
G
C
B
I
H
D
H
Battery terminals
H
Battery terminals
Item
A
B
C
D
E
H
F
G
Description
AC terminals
Grounding bar
PV terminals
Communication out terminal
Gateway 2030.5 antenna terminal
Communication in terminal
AUX terminal
MLPE terminal
I
Battery terminals
2. The standard series number rules is as follows: