6.2.1 PV Connection
WARNING!
Select PV modules with excellent functioning and reliable quality.
Open-circuit voltage of module arrays connected in series
should be less than the inverter Max. DC input voltage of 550V.
The inverter warranty is VOID if the DC input voltage is
exceeded.
WARNING!
Ensure no live voltages are present on the PV input and AC
output circuit, and verify that the DC disconnect, AC disconnect,
and dedicated AC circuit breaker are in the “OFF” position
before installation.
WARNING!
Use dark, opaque sheets to cover the PV solar panels before
performing any wiring or connection.
WARNING!
Power is fed from more than one source and more than one live
circuit. Note that all DC and AC terminals may carry current even
without connected wires.
WARNING!
Ensure maximum protection against hazardous contact voltages
while assembling PV panel installations. Both the positive and
negative leads must be strictly isolated electrically from the
protective ground potential (PE).
CAUTION!
Never reverse the polarity of the array string cables as it can
cause damage to the inverter. Always ensure correct polarity.
Electrical Connection
Electrical Connection
41
40
NOTE!
The PV connection mode below is NOT allowed!
Inverter
PV Array
PV1
PV2
+
-
+
-
+
-
+
-
+
-
x
A1-HYB G2 Series inverter can be connected with PV modules in series with
-
2
MPPTs for A1-HYB-3.8K-G2, A1-HYB-5.0K-G2 and A1-HYB-6.0K-G2, 3 MPPTs
for A1-HYB-7.6K-G2
.
PV String Connection
Ø
A: PV1 Positive terminal B: PV1 Negative terminal
C: PV2 Positive terminal D: PV2 Negative terminal
E: PV3 Positive terminal F: PV3 Negative termina
l
A
B
C
D
E
F
√
Inverter
PV
PV1
PV2
+-
+-
+
-
+
-
+
The inverter supports the following PV module
connection modes.