NOTE
Make sure the mounting surface or structure can support the weight of the
inverter.
CAUTION!
SolarEdge inverters and power optimizers can be installed at a minimum
distance of 50 m/ 164 ft from the shoreline of an ocean or other saline
environment, as long as there are no direct salt water splashes on the inverter or
power optimizer.
1. Determine the inverter mounting location, on a wall, stud framing or pole. It is
recommended to mount the inverter in a location protected from direct sunlight.
2. To allow proper heat dissipation, maintain the following minimum clearance areas
between the inverter and other objects:
Figure 9: Clearance areas
If installing a single inverter:
20 cm (8") from the top of the inverter.
At least 10 cm (4") from the bottom of the inverter.
10 cm (4") from the right and left of the inverter.
If installing multiple inverters:
When installing inverters side by side, leave at least 20 cm (8") between
inverters.
When installing inverters one above of the other, leave at least 40 cm (16")
between inverters.
3. Position the mounting bracket against the wall/ pole and mark the drilling hole
locations (refer to
Mechanical Specifications on page 64 for inverter and mounting
bracket dimensions).