![SolarEdge OP250-LV Installation Manual Download Page 33](http://html1.mh-extra.com/html/solaredge/op250-lv/op250-lv_installation-manual_1313700033.webp)
Installing the Inverter
SolarEdge Installation Guide – MAN-01-00002-1.6
33
WARNING!
You should also refer to the technical specifications in
Appendix B, Technical
Specifications
on page 108. Pay special attention to the inverter specifications
because they may differ slightly in different countries.
Vous devriez également consulter les spécifications techniques de l'annexe B,
Spécifications techniques à la page 108. Portez une attention particulière aux
spécifications de l’onduleur, car elles peuvent varier légèrement selon les pays.
WARNING!
It is essential to connect the PE (ground) wiring before connecting the AC Line
and Neutral wires.
Il est essentiel de connecter le câble PE (la terre) avant de connecter les lignes
AC et Neutre.
WARNING!
Grounding of the DC-side current-carrying conductors is prohibited because the
Single Phase Inverter has no transformer.
Mise à la terre du coté
des conducteurs de courant CC
est
interdite
car l'onduleur
monophasé n'a pas de transformateur.
NOTES
Functional Electrical Earthing of DC-side negative or positive is prohibited
because the Single Phase Inverter has no transformer.
Earthing of PV array module frames and mounting equipment (equipotential