![SolarEdge L20-IB60, L20-IB00 Installation Manual Download Page 69](http://html1.mh-extra.com/html/solaredge/l20-ib60-l20-ib00/l20-ib60-l20-ib00_installation-manual_1313774069.webp)
61
L20, L30
13.
Appendix 8 REPO instruction
13.1.
Port definition
Figure 41 REPO port
Table 22 Connection between the button and UPS REPO port
Button
UPS REPO
Description
Pin 1
Pin 1
EPO-NO
Pin 2
Pin 2
EPO-12V
Pin 1
Pin 3
EPO-NC
Pin 2
Pin 4
EPO-12V
A remote emergency stop switch can be installed in a remote location and connection
through simple wires to the REPO connector.
Summary of Contents for L20-IB60, L20-IB00
Page 2: ......
Page 17: ...9 L20 L30 Figure 5 Install covers...
Page 27: ...19 L20 L30 5 5 Cabinet view Figure 15 Front view Side view of L20 and L30...
Page 31: ...23 L20 L30 5 7 Electrical Diagrams Figure 19 Remote EPO NO and NC port...
Page 32: ...24 L20 L30 Figure 20 External maintenance bypass auxiliary contacts...