48
L20, L30
Model
L20
L30
Frequency tolerance
40-70Hz
Voltage window (At
100%/50% load)
176-280Vac or 305-485Vac, Full load
80-280Vac or 138-485Vac, <40% Load
Back feed contact point
Dry contact: 125Vac/0.5A
Power Walk IN(S) for parallel
system
0-200
Dual feed
Standard with busbar configuration as single feed
Input rate current(A)
32/31/30A
48/46/44A
Input max. current(A)
40/38/37A
60/57/55A
Battery
Battery types
VRLA
Build-in battery
60pcs 9Ah
60pcs 9Ah
±
120Vdc
±
180Vdc
Battery block flexibility
Optional Voltage:
±
96/108/120/132/144/156Vd
c (16/18/20/22/24/26pcs
optional)
192Vdc
~
312Vdc
(16~26pcs, 20 pcs define,
20~ 26pcs no power
derating; 18pcs output
power factor 0.9;16pcs
output power factor 0.8;)
Optional Voltage:
±180/±192/±204/±216/±2
28/±240/±252/±264/±276/
±288/±300Vdc(30/32/34/3
6/38/40/42/44/46/48/50pcs
optional)
360Vdc~600Vdc (30~50
pcs, 30 pcs define, 36~ 50
pcs no power derating;
32~34 pcs output power
factor 0.9;30 pcs output
power factor 0.8;)
Charge capacity
13A Max.
Battery temperature
compensation (standard /
optional)
40
℃
/104
°
F
>
T
>
25
℃
/
82.4
°
F , -7~0mV/
℃
,
default
:
no compensation
Battery test
Manual and automatic programmable by time or voltage
Summary of Contents for L20-IB60, L20-IB00
Page 2: ......
Page 17: ...9 L20 L30 Figure 5 Install covers...
Page 27: ...19 L20 L30 5 5 Cabinet view Figure 15 Front view Side view of L20 and L30...
Page 31: ...23 L20 L30 5 7 Electrical Diagrams Figure 19 Remote EPO NO and NC port...
Page 32: ...24 L20 L30 Figure 20 External maintenance bypass auxiliary contacts...