L20, L30
12.3.
Backfeed installation with relay:
1. Connect the UPS backfeed dry contact to a terminal of the relay R coil. Route the cable
with the other signal cables.
2. Connect the fuse F, the auxiliary contact of relay R, and the coil of C as shown in the
illustration below.
3. Connect C (L1, L2 , L3) with UPS bypass input (L1, L2, L3) as shown in the illustration below.
4. Connect bypass input (N) with mains feeding (N) in the distribution switchgear.
Figure 40 Backfeed diagram