SE15K
SE16K
SE17K
SE25K
SE27.6K
SE33.3K
Unit
Maximum continuous
overcurrent protection
23
25.5
26
38
40
40
A
Residual current detector /
Residual Current step detector
300 / 30
mA
Grid supported – three phase
3 / N / PE (WYE with Neutral)
V
Inrush current AC (Peak/
Duration)
3/ 20
3.1/ 20
4.2/ 20
Aac(rms) /
ms
Maximum output fault current
65
72
68
88
92
92
A
Power factor range
1 (adjustable from -0.9 to +0.9)
1 (adjustable from -0.8 to +0.8)
(1)
Total harmonic distortion
< 3%
Protective class
Class I
Utility monitoring, islanding
protection, configurable Power
Factor, country configurable
thresholds
Yes
Overvoltage category
III
Input
Maximum DC power (Module
STC)
20250
21600
22950
33750
37250
45000
W
Transformer-less, ungrounded
Yes
Maximum input voltage
900
1000
Vdc
Nominal DC input voltage
750
840
Vdc
(1)
For SE27.6K - when set to Germany Power Factor is limited to 0.9.
SolarEdge
-
Three Phase System MAN-01-00505-1.5
78