Technical Specifications - Three Phase Inverters (Europe & APAC)
SE4K - SE12.5K
SE3K
SE4K
SE5K
SE6K
SE7K
SE8K
SE9K
SE10K
SE12.5K
Unit
Output
Rated AC power output
3000
(1)
4000
(1)
5000
6000
(1)
7000
8000
9000
10000
12500
VA
Maximum AC power
output
3000
4000
5000
6000
7000
8000
9000
10000
12500
VA
AC Output Line
Connections
3 phase, 4-wire / PE (L1-L2-L3-N), TN, TT
AC output voltage – line to
line / line to neutral
(nominal)
380/ 220; 400/ 230
Vac
AC output voltage range
184 – 264.5
Vac
AC frequency
50/60 ± 5
Hz
Maximum continuous
output current (per phase)
5
6.5
8
10
11.5
13
14.5
16
20
A
Maximum continuous
overcurrent protection
5
6.5
8
10
11.5
13
14.5
16
20
A
Residual current detector /
Residual Current step
detector
300 / 30
mA
(1)