background image

8. Winterization

1. Winterize pool with air as you normally would.  Make sure that power is off to the SolarAttic

pool heater and that the pump is disconnected.

2. Blow air through the PCS3 pipes using a shop vacuum or other tool until all water is removed.

3. Perform all other winterization chores.

4. Make sure all pipes by support system are drained completely or they will freeze and bust.  Any

suspect pipes having “trapped” water should have a hole drilled and a plug installed for winter
draining.

5. Remove the PCS3’s outlet and inlet unions.  Tilt the opposite side up two inches and drain any

coil water into a pan.  Next, tilt the inlet/outlet side up two inches followed by a second tilt of the
opposite side for draining any additional coil water into the pan.  Repeat this process until no 
water drains from the PCS3.

6. Pour 1/2 to 1 gallon of RV [recreational vehicle] non-toxic antifreeze into the bottom of the

PCS3.  Note: This dilutes any residual “trapped” water still remaining within the coil and insures
no freeze damage.  This is the same type of antifreeze used in the pool’s pump and skimmers
during the winterization process! It is similar to the process used to winterize RV’s and cabins.

7. Reinstall the outlet and inlet unions.

8. The PCS3 is winterized.

CAUTION

: Failure to follow Step #6 above can lead to water coil damage!  Even 

after Steps #1-5, the PCS3 water coil could still retain a small amount of residual 
water that is “trapped” within the bottom of the coil.  The non-toxic “RV” antifreeze
[available at local hardware stores] dilutes any residual water and prevents winter
freeze damage.  Winter freeze damage is totally preventable and is not covered under
the PCS3 Warranty.  It is the owner’s responsibility to have the system winterized.

Bypass Valve Consideration

In the process of winterization, air is blown through all of the pipes to eliminate water inside of the pipes
[and all valves].  The bypass valve should be exercised in both directions a few times to eliminate all of
the water within the valve.  This can be accomplished using the manual on/off function of the GL235 or
by manually turning the valve in both positions [with valve motor removed].  This should eliminate all
water inside the bypass valve.

There have been two reported incidents of cracked bypass valves during spring start-up.  The bypass
valves were found to be cracked along the underside of the valve.  This indicates that water was inside
the valve during a freeze.  This was probably the direct result of either: A) An improper winterization 
effort; or, B) A bypass valve that is installed in such a position to either “trap” or “collect-back” water
into its base.  After the pipes have been drained, a small amount of trapped water or moisture may still
be present in some of the pipes or valves depending upon how the system is plumbed.  If the bypass
valve represents such a “trap” or a “collection point” for residual drain-back within the plumbing, it may
cause damage to the valve.   Water that freezes needs expansion space.

- 18 -

Summary of Contents for PCS3

Page 1: ...Installation and Operating Instructions SolarAttic Solar Pool Heater Pool Convection System Three U S Patents 5 014 770 5 452 710 5 746 653 SolarAttic Model PCS3...

Page 2: ...This page intentionally left blank...

Page 3: ...m 6 7 Basic Plumbing Diagram 8 Power The PCS3 9 Internal Wiring Diagram 10 Float Wiring Diagram 11 Goldline GL235 Solar Control 12 Goldline GL235 Circuit Board 13 Automation Wiring Diagram 14 Goldline...

Page 4: ...tion strikes the roof and reaches the attic through a process called conduction The SolarAttic pool heater is physically located inside the attic and then transfers this solar radiation from the attic...

Page 5: ...wered from the actual attic peak heat transfer performance can be dramatically reduced 7 The pool water sensor can be influenced by the sun and rain Shelter the pool water sensor as much as is possibl...

Page 6: ...VERED BY THE MANUFACTURERS WARRANTY ASSEMBLE THE VALVES AND PIPES BEFORE ACTUAL WELDING TO MAKE SURE THE JOINTS FIT PROPERLY THIS INSURES YOUR PARTS ARE READY FOR PERMANENT CEMENTING PLUMBING CAUTION...

Page 7: ...BLE AND DOES NOT SMELL OF CHLORINE YOU HAVE THE RIGHT POOL CHEMISTRY CHECK WITH YOUR LOCAL POOL CHEMICAL DEALER IF YOUR POOL DOES NOT HAVE THESE ATTRIBUTES BUILDING CODE CAUTION INSTALL ALL EQUIPMENT...

Page 8: ...mating pvc female fittings to the copper pipe threads we recommend using silicone sealant and allowing the joints to properly cure for 24 hours before placing them into use Do not use teflon tape Loca...

Page 9: ...ort systems located far away from the attic can be relocated closer by extending the pool s support piping Extremely long pipe runs may require added horsepower from the pool s pump If your pump is in...

Page 10: ...I I I IN N N N R R R RE E E ET T T TU U U UR R R RN N N N L L L LI I I IN N N NE E E ES S S S PUMP S S S ST T T TR R R RA A A AI I I IN N N NE E E ER R R R I I I IN N N NT T T TA A A AK K K KE E E E P...

Page 11: ...Note Place the attic sensor above the PCS3 out of the air flow and at the apex or peak of the attic The discharge air of the PCS3 can cool the temperature sensor down causing erratic cycling on off of...

Page 12: ...on this speed If the blower just hums this motor starting capacitor will have to be replaced Turn the power off remove the electrical cover panel and replace the capacitor Ensure the new capacitor is...

Page 13: ...pret the open circuit as a cold attic and shut down the PCS3 An open float also results in a flashing check sensor red light on the Goldline GL235 solar control The PCS3 must operate in the AUTO mode...

Page 14: ...Goldline GL235 Solar Control 12...

Page 15: ...Goldline GL235 Circuit Board 13...

Page 16: ...2 No connection 3 115 vac Hot Side from timer black 4 115 vac Neutral from timer white 5 115 vac Hot Side from timer to GL 235 Relay black 6 115 vac Hot Side from Relay to SolarAtttic Outlet black Ne...

Page 17: ...15 Goldline Wiring Option 220 VAC...

Page 18: ...llations maximum heat extraction is limited by human intervention or semi automated devices like switches or timers However heat extraction can be easily maximized and automated by way of an optional...

Page 19: ...need to be changed Note This is also a very rare occurrence 6 Some evidence of a small amount of condensate will be present in the form of a water stain in the interior of the PCS3 base pan This is n...

Page 20: ...amount of residual water that is trapped within the bottom of the coil The non toxic RV antifreeze available at local hardware stores dilutes any residual water and prevents winter freeze damage Winte...

Page 21: ...ssibility of a period of one or more days when temperatures below freezing are occurring or being forecasted by prevailing weather OR you may be simply late in getting around to winterizing your pool...

Page 22: ...e entire assembly can also be completely dismantled using only a few tools a a portable drill or electric drill b a 5 16 hex head bit c a No 2 phillips screwdriver or drill bit and d two 1 2 socket or...

Page 23: ...e 6 Internal PCS3 blower motor thermal cutoff Wait 15 minutes for it to cool off then retry 7 Defective PCS3 power cord or plug 8 Defective Motor starting capacitor 9 Defective Motor 10 Defective Sola...

Page 24: ...rnal limit switch needs adjusting 2 Internal cam needs adjusting 3 Internal mechanical stop needs adjusting 4 Defective valve operator Replace TEST Reverse the VOR Switch Turn it from ON1 to the ON2 p...

Page 25: ...disconnected sensor wires 1 Poor solar weather No Sunshine 2 Pump Timer out of sync with solar energy collection time causing pool to cool too much time 3 Water flow valves to PCS3 are shut off or re...

Page 26: ...waterfall It masks performance of PCS3 or offsets the heat gains of the PCS3 Waterfalls on a pool can have a dramatic cooling effect on pool temperature 1 Pool water temperature sensor exposed to coo...

Page 27: ...size of the filter pump 3 Slave the filter pump to the GL235 power relay us ing an external relay as shown online and also use a minimum runtime timer This will ensure that only the minimum filtration...

Page 28: ...nd the products they manufacture receive regular ETL safety reviews during each year to maintain product safety certifications When you buy the PCS3 you can have full confidence that the SolarAttic pr...

Page 29: ...Single Speed Noise 62 db A weighted 67 db C weighted 10 feet Plumbing Connections 2 Male Pipe Threads Pressure Drop 4 6 PSI typical Air Flow Rate 2600 SCFM Water Flow Rate Range 15 65 GPM Optimal Wate...

Page 30: ...They are waffled in appear ance and not straight Fin bending that has been combed with a fin tool does not affect performance and is not considered a manufacturing defect Our obligation under this war...

Page 31: ...This page intentionally left blank...

Page 32: ...5 West Veum Appleton Minnesota 55311 www solarattic com 2003 2016 All Rights Reserved Version 1 5 ETL Contents subject to change Original Appleton Minnesota Manufacturing Crew in 2003 Made In The U S...

Reviews: