Manual 2100-707D
Page
29 of 39
TABLE 10
Electrical Specifications
−
J**AB Series
Model
Rated
Volts
& Phase
No.
Field
Power
Circuits
Single Circuit
Multiple Circuit
Minimum
Circuit
Ampacity
Maximum
External
Fuse or
Ckt. Brkr.
Field
Power
Wire
Size
Ground
Wire
Minimum
Circuit
Ampacity
Maximum
External Fuse
or
Ckt. Breaker
Field Power
Wire Size
Ground
Wire Size
Ckt.
A
Ckt.
B
Ckt.
A
Ckt.
B
Ckt.
A
Ckt.
B
Ckt.
A
Ckt.
B
J18AB-A00, A0Z
A05
A08
A10
230/208-1
1
1
1
1
16
30
45
56
20
30
45
60
12
10
8
6
12
10
10
10
J24AB-A00, A0Z
A05
A08
A10
230/208-1
1
1
1
1
21
30
46
57
25
30
50
60
10
10
8
6
10
10
10
10
J24AB-B00, B0Z
B06
230/208-3
1
1
15
23
20
25
12
10
12
10
J24AB-C00, C0Z
C06
460-3
1
1
8
12
15
15
14
14
14
14
J30AB-A00, A0Z
A05
A08
A10
A15
230/208-1
1
1
1
1
1 or 2
23
31
47
57
83
35
35
50
60
90
8
8
8
6
4
10
10
10
10
8
57
26
60
30
6
10
10
10
J30AB-B00, B0Z
B06
B09
B15
230/208-3
1
1
1
1
17
23
32
50
20
25
35
50
12
10
8
8
12
10
10
10
J30AB-C00, C0Z
C06
C09
C12
C15
460-3
1
1
1
1
1
9
12
16
21
25
15
15
20
25
25
14
14
12
10
10
14
14
12
10
10
J36AB-A00, A0Z
A05
A08
A10
A15
230/208-1
1
1
1
1
1 or 2
27
32
48
58
84
35
35
50
60
90
8
8
8
6
4
10
10
10
10
8
58
26
60
30
6
10
10
10
J36AB-B00, B0Z
B06
B09
B15
230/208-3
1
1
1
1
20
24
33
51
25
25
35
60
10
10
8
6
10
10
10
10
J36AB-C00, C0Z
C06
C09
C15
460-3
1
1
1
1
11
12
17
26
15
15
20
30
14
14
14
12
14
14
14
12
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest
version), Article 310 for power conductor sizing.
CAUTION
: When more than one field power circuit is run through one conduit, the
conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than
three (3) current carrying conductors are in a raceway.
Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
Based on 75°copper wire. All wiring must conform to the National Electrical Code and all local codes.
NOTE:
The Maximum Overcurrent Protection (MOCP) value listed is the maximum value as per UL 1995 calculations for MOCP (branch-
circuit conductor sizes in this chart are based on this MOCP). The actual factory-installed overcurrent protective device (circuit
breaker) in this model may be lower than the maximum UL 1995 allowable MOCP value, but still above the UL 1995 minimum
calculated value or Minimum Circuit Ampacity (MCA) listed.
IMPORTANT:
While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor
wires in accordance with the National Electrical Code and all local codes.