background image

Manual 2100-707D 

Page 

28 of 39

TABLE 9 

Cooling Pressure 

 Balanced Climate Airflow

Air Temperature Entering Outdoor Coil °F

Low side pressure ± 4 PSIG                                                         
High side pressure ± 10 PSIG
Tables are based upon Balanced Climate CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge 
being in the system, the charge should be removed and system evacuated and recharged to serial plate charge weight.

NOTE:

 Pressure table based on high speed condenser fan operation. If condensing pressures appear elevated check condenser fan wiring. 

See 

Condenser Fan Operation

 on page 21.

Model

Return Air Temp 

(DB/WB)

Pressure

75

80

85

90

95

100

105

110

115

120

125

131

W18A/L

75/62

Low Side

High Side

117
295

119
317

121
338

122
362

124
385

126
410

129
436

131
463

133
491

135
520

137
550

139
587

80/67

Low Side

High Side

125
303

127
325

129
347

131
371

133
395

135
421

138
447

140
475

142
504

144
533

146
564

149
602

85/72

Low Side

High Side

129
314

131
336

134
359

136
384

138
409

140
436

143
463

145
492

147
522

149
552

151
584

154
623

W24A/L

75/62

Low Side

High Side

116
296

118
318

120
339

122
362

123
385

125
410

128
434

130
460

132
488

135
515

137
544

139
579

80/67

Low Side

High Side

124
304

126
326

128
348

130
371

132
395

134
420

137
445

139
472

141
500

144
528

146
558

149
594

85/72

Low Side

High Side

128
315

130
337

132
360

135
384

137
409

139
435

142
461

144
489

146
518

149
546

151
578

154
615

W30A/L

75/62

Low Side

High Side

117
312

120
334

122
357

124
381

126
406

128
432

130
458

132
486

134
514

135
543

137
572

138
609

80/67

Low Side

High Side

125
320

128
343

130
366

133
391

135
416

137
443

139
470

141
498

143
527

144
557

146
587

148
625

85/72

Low Side

High Side

129
331

132
355

135
379

138
405

140
431

142
459

144
486

146
515

148
545

149
576

151
608

153
647

W36A/L

75/62

Low Side

High Side

120
312

122
332

123
354

124
377

126
402

128
427

130
454

132
483

135
513

137
543

138
576

141
616

80/67

Low Side

High Side

128
320

130
341

132
363

133
387

135
412

137
438

139
466

141
495

144
526

146
557

148
591

151
632

85/72

Low Side

High Side

132
331

135
353

137
376

138
401

140
426

142
453

144
482

146
512

149
544

151
576

153
612

156
654

Summary of Contents for J AB Series

Page 1: ...ioner Models INSTALLATION INSTRUCTIONS J18AB A J24AB A J24AB B J24AB C J30AB A J30AB B J30AB C J36AB A J36AB B J36AB C Manual 2100 707D Supersedes 2100 707C Date 2 3 21 J18LB A J24LB A J24LB B J30LB A...

Page 2: ...on Make Timer 22 Short Cycle Delay on Break 22 Low Pressure Detection 23 High Pressure Detection 23 Test Mode 23 Brownout Protection with Adjustment 23 Pressure Service Ports 23 Service 24 Troublesho...

Page 3: ...ne 212 642 4900 Fax 212 302 1286 ASHRAE American Society of Heating Refrigeration and Air Conditioning Engineers Inc 1791 Tullie Circle N E Atlanta GA 30329 2305 Telephone 404 636 8400 Fax 404 321 547...

Page 4: ...unit These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Not...

Page 5: ...metallic return air grille is required with installations not requiring a return air duct The spacing between louvers on the grille shall not be larger than 5 8 Any grille that meets with 5 8 louver c...

Page 6: ...hinder unit installation and servicing including outdoor electrical conduits junction boxes wall drains vent hoods windows doors overhangs and posts Condensate Water Drainage Review all codes and requ...

Page 7: ...ructure through ventilation options including fresh air dampers ventilators economizers and energy recovery ventilators Be sure to install the return grille with the louvers pointed downward towards t...

Page 8: ...ark bolt hole locations and bottom mounting bracket location Install bottom mounting bracket with field supplied fasteners to wall if it is to be used optional Bracket must be level and installed in t...

Page 9: ...unit and J A right side compressor and controls for right unit See Specifications Sheet S3582 TABLE 1 Clearance Required for Service Access and Adequate Condenser Airflow Model Left Side Right Side D...

Page 10: ...lectrical Entrances Side Wall Supply Air Opening Shipping Location Brackets Return Air Opening Built In Mounting Top Rain Flashing Bottom Installation Bracket Back View 44 O E R S S S S S T N B P M L...

Page 11: ...and Hole Location View Right Side View TOP FLASHING AT TIME OF INSTALLATION OPENING MIS 3157 A ENTIRE LENGTH OF TOP TOP NOTES OF CAULKING ALONG PANEL FOAM AIR SEAL WALL STRUCTURE WALL HEATER ACCESS RA...

Page 12: ...NOTES 1 4 CLEARANCE ON ALL HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER SILICONE CAULKING BE PLACED BEHIND IS ON OPPOSITE LEFT SIDE OPENING CONTROLS AND HEAT...

Page 13: ...SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1 4 CLEARANCE TO COMBUSTIBLE SURFACES Fire hazard Maintain minimum 1 4 clearance between the supply air duct and combustible materials in...

Page 14: ...CTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACTU...

Page 15: ...best unit performance and efficiency Review duct grille or return duct work Avoid using restrictive duct work to Unit Mount Return Grille Fixed Blade Wall wall Outside Wall Ducted Installations Adjus...

Page 16: ...or airflow amount and extending the run time to help extract more humidity during cooling operation In heating mode the reduced airflow provides a warmer supply air temperature creating more comfortab...

Page 17: ...ration cycles the condenser fan on off to maintain desired liquid pressure while modulating LAC operation is factory adjusted and slows the condenser fan speed rpm Outdoor Temperature Switch and Freez...

Page 18: ...6 B 4 5 7 If not equipped with a ventilation option to plug in a jumper plug must be installed 4 2 8 9 TABLE 6 Wall Thermostats Part Number Predominate Features 8403 060 1120 445 3 stage Cool 3 stage...

Page 19: ...ntrol Optional for ECON Only See vent installation manual 6 For vent operation add jumper if optional CO2 controller is not used Vent will run while blower is energized For ECON CRV V an additional wi...

Page 20: ...refrigerant it must come out of the charging cylinder tank as a liquid to avoid any fractionation and to ensure optimal system performance Refer to instructions for the cylinder that is being utilized...

Page 21: ...filters at all times and also not to needlessly close off supply and return air registers This reduces airflow through the system which shortens equipment service life as well as increasing operating...

Page 22: ...ied with a factory installed vent package it will be plugged in but the jumper plug will also be tethered next to the connection for troubleshooting purposes if necessary Compressor Control Module The...

Page 23: ...mers can be set by DIP switches in order to delay signaling a power brownout for a specific length of time after compressor contactor is energized This allows the compressor a time period to start eve...

Page 24: ...3302 PA13362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 Series Motors TROUBLESHOOTING GE X13 SERIES ECM2 3 MOTORS If the Motor is Running 1 It is normal for the motor to rock back a...

Page 25: ...utput 24VAC Common 24VAC Common 24VAC R Signal through thermostat output 2 If the motor has proper high voltage and ground at the L L1 G N L2 connections then continue with the Model SelecTech Communi...

Page 26: ...unit to the serial plate charge Removal of Fan Shroud 1 Disconnect all power to the unit 2 Remove the screws holding both grilles one on each side of unit and remove grilles 3 Remove nine screws hold...

Page 27: ...de High Side 132 315 136 337 140 361 143 386 146 412 148 439 151 467 153 495 154 525 156 556 157 587 159 626 J24A L 75 62 Low Side High Side 123 302 125 323 127 344 129 367 132 391 134 415 136 441 137...

Page 28: ...138 409 140 436 143 463 145 492 147 522 149 552 151 584 154 623 W24A L 75 62 Low Side High Side 116 296 118 318 120 339 122 362 123 385 125 410 128 434 130 460 132 488 135 515 137 544 139 579 80 67 Lo...

Page 29: ...3 51 25 25 35 60 10 10 8 6 10 10 10 10 J36AB C00 C0Z C06 C09 C15 460 3 1 1 1 1 11 12 17 26 15 15 20 30 14 14 14 12 14 14 14 12 These Minimum Circuit Ampacity values are to be used for sizing the field...

Page 30: ...460 3 1 1 1 9 15 24 15 15 25 14 14 10 14 14 10 These Minimum Circuit Ampacity values are to be used for sizing the field power conductors Refer to the National Electrical code latest version Article 3...

Page 31: ...black wire on the blower speed terminal block to either MED or HI Refer to Table 14 on page 33 for the corresponding airflow of each tap Set the unit duct static based on the highest airflow that the...

Page 32: ...s used when Balanced Climate is called for by energizing the Y1 terminal of the low voltage terminal block with 24VAC Speed tap 2 is overridden if taps 3 4 or 5 are energized Speed Tap 3 Default LO Co...

Page 33: ...770 755 910 885 955 930 0 25 740 730 890 865 935 910 0 30 715 705 870 840 915 885 0 40 670 650 825 805 870 845 0 50 630 585 785 765 825 805 J30AB J30LB 0 00 830 825 1050 1020 1170 1135 1200 1205 0 10...

Page 34: ...igh Low A0Z A05 A08 A10 A15 50 50 50 30 50 50 50 40 40 50 50 50 35 35 B0Z B06 B09 B15 50 40 50 50 50 35 50 40 50 30 C0Z C06 C09 C15 50 50 50 50 50 45 50 50 40 35 TABLE 16 Electric Heat Models 240V 1 2...

Page 35: ...cription CMC 15 Start Kit 230V 1 Phase X X FAD NE2 Fresh Air Damper No Exhaust X ECONS 3 Economizer School X ECONWD 2 Economizer Bldg Equipment Enthalpy or Temperature X FAD NE3 Fresh Air Damper No Ex...

Page 36: ...HW2TAB A08 X EHW2TA A10 X X EHW2TA B06 X EHWH24B C06 X EHW3TA A05 X X EHW3TA A08 X X EHW3TA A10 X EHW3TAB A10 X EHW3TA A15 X EHW3TAB A15 X EHW30A B06 X EHW3TA B06 X EHW3TA B09 X EHW3TAB B09 X EHW3TA B...

Page 37: ...1TAB A08L X EHW2TAB A05L X EHW2TAB A08L X EHW2TA A10L X X EHW2TA B06L X EHW3TA A05L X X EHW3TA A08L X EHW3TA A10L X EHW3TAB A10L X EHW3TA A15L X X EHW3TA B09L X EHW3TAB B09L X EHW3TA B15L X EHW3TAB B1...

Page 38: ...Manual 2100 707D Page 38 of 39 GRAPH 1 J18 B FAD NE2 3 W O Exhaust Ventilation Delivery GRAPH 2 J24 B FAD NE2 3 W O Exhaust Ventilation Delivery...

Page 39: ...Manual 2100 707D Page 39 of 39 GRAPH 3 J30 B FAD NE2 3 W O Exhaust Ventilation Delivery GRAPH 4 J36 B FAD NE2 3 W O Exhaust Ventilation Delivery...

Reviews: