solaia SL375 THRU Installation And Operator'S Manual Download Page 6

 

6

hundred (100) square inches.  These openings must freely communicate with the interior areas having adequate 

infiltration from the outside.  

 

When the boiler is installed in a confined space and all air is provided from the outdoors, the confined space 
shall be provided with two permanent openings. One commencing within 12 inches from the top, and one 
commencing 12 inches from the bottom of the enclosure.  The openings shall communicate directly, or by 
ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.  One of the 
following methods must be used to provide adequate air for ventilation and combustion. 

 

1.

 

When directly communicating with the outdoors, each opening shall have a minimum free area of 1 
square inch per 4,000 BTU per hour of total input rating of all equipment in the enclosure.  

2.

 

When communicating with the outdoors by means of vertical ducts, each opening shall have a minimum 
free area 1 square inch per 4,000 BTU per hour of total input rating of all appliances in the enclosed 
space.   

3.

 

If horizontal ducts are used, each opening shall have a minimum free area 1 square inch per 2,000 BTU 
per hour total input rating of all appliances in the enclosed space.  

4.

 

When ducts are used, they shall be on the same cross sectional are as the free area of the openings to 
which they connect.  The minimum dimensions of rectangular air ducts shall not be less than 3 inches. 

 

In calculating free area using louvers, grills or screens for the above, consideration shall be given to their 
blocking effect.  Screens used shall not be smaller than ¼ inch mesh.  If free area through a design of louver 
of grill is known, it should be used in calculating the size opening required to provide the free area specified.  
If the design and free area is knot known, it may be assumed that wood louvers will have 20-25% free area 
and metal louvers and grills will have 60-75% free area.  Louvers and grills shall be fixed in the open 
position or interlocked with the boiler so that they are opened automatically during boiler operation.  

 

Boiler Assembly

 

 

LOCATE BOILER…

in front of final position before removing crate.  

PROVIDE A LEVEL

 

SOLID BASE

 as near chimney or direct vent as possible and centrally located with 

respect to the heat distribution system as practical. 
The boiler must be placed within distances from boiler room walls and ceilings that comply with existing 
building codes and for ease of service

 

THE PACKAGED BOILER IS SHIPPED IN TWO PACKAGES

a.

 

Boiler and Cabinet Assembled and Crated  

b.

 

Burner/Parts Box – Includes burner, aquastat and trim piping 

 

LOCATE THE BOILER in the position to be assembled and piped. 

 

Remove crate,

 

plastic protective wrapper and INSPECT FOR DAMAGE.  All equipment is carefully 

manufactured, inspected and packaged by experienced workers.  Our responsibility ceases upon delivery of 
the crated boiler to the carrier in good condition.  ANY CLAIMS FOR DAMAGE OR SHORTAGE IN 
SHIPMENT MUST BE FILED IMMEDIATELY against the carrier by the consignee. 
 

Temperature Controls Installation and Adjustment 

1.

 

Install the temperature control on the right side of the boiler.  Attach the Honeywell L7248C aquastat or 
the Hydrostat 3250 to the jacket side panel using sheet metal screws and the holes provided in the jacket 
panel.  The sensor wires should be run through the bottom knockout in the aquastat.  The rubber 
grommet provided with the sensor wires is to be securely inserted into the aquastat knockout. 

2.

 

Connect the sensor leads to the appropriate temperature control terminals. 

3.

 

Connect your line voltage and thermostat wires if applicable to the control. See electrical diagrams for 
proper connections. 

4.

 

The overall range of the High Limit is from 130

0

F to 220

0

F. Typically it would be set in the range of 

180

0

F to 200

0

F.   

 

Summary of Contents for SL375 THRU

Page 1: ...ATOR S MANUAL SL375 THRU SL7175 CAST IRON BOILERS Keep these instructions with the boiler at all times for future reference BOYERTOWN FURNACE CO PO Box 100 BOYERTOWN PA 19512 1 610 369 1450 www boyert...

Page 2: ...erty damage Your oil fired boiler is designed to burn No 1 and No 2 heating oil only Never use gasoline or a mixture of gasoline and oil Do not store gasoline or other flammable vapors and liquids in...

Page 3: ...n Tanks Venting Systems 8 Chimney Venting Direct Venting Burner Installation 13 Oil Tank and Piping 13 Gas Piping 14 Wiring 14 Swing Door 17 Opening the Door Closing the Door Door Hinge Reversal Opera...

Page 4: ...19 1 4 19 1 4 22 3 4 22 3 4 26 1 4 26 1 4 29 3 4 33 1 4 Supply Outlet Height 25 3 8 25 3 8 25 3 8 25 3 8 25 3 8 25 3 8 25 3 8 25 3 8 Return Outlet Height 4 1 2 4 1 2 4 1 2 4 1 2 4 1 2 4 1 2 4 1 2 4 1...

Page 5: ...all times Ventilation of boiler room must be adequate enough to provide sufficient air for combustion When a boiler is located in an unconfined space in a building of conventional frame or masonry con...

Page 6: ...wn it may be assumed that wood louvers will have 20 25 free area and metal louvers and grills will have 60 75 free area Louvers and grills shall be fixed in the open position or interlocked with the b...

Page 7: ...BY TECHNICALLY QUALIFIED SERVICEMEN SOLAIA BOILERS HAVE A MAXIMUM OPERATING PRESSURE OF 58PSI NOTE If normal operating pressures are greater than 30psi please contact the manufacturer for required tri...

Page 8: ...in to conform to code standards Discharge piping from the relief valve must be piped to a drain or must terminate 6 above the floor to eliminate damage to the structure or personal injury It must not...

Page 9: ...he boiler should comply with applicable building codes such as NFPA 211 An additional listed lining may be required to reduce transient low draft during startup and acid water condensation during cycl...

Page 10: ...he chimney must be made above the bottom of the chimney to avoid blockage Vent piping should extend just into the chimney far enough to expel flue gasses Inserting the vent piping too far into the chi...

Page 11: ...system must conform to the following guidelines See figure on following page a The vent terminal shall not be less than 3 feet above any forced air inlet to the house b The vent terminal shall not be...

Page 12: ...ANCE TO COMBUSTIBLE MATERIALS FROM THE DOUBLE WALL INSULATED VENT PIPING IS 2 CONSULT NFPA 31 FOR REDUCED CLEARANCES The air intake must be installed to the air inlet collar on the combination vent ho...

Page 13: ...correct nozzle is properly installed in the burner as shown in the preliminary burner settings and that the burner electrodes are adjusted as per the burner manual When using the Beckett AFG Carlin EZ...

Page 14: ...00 242 000 180 100 000 255 000 Note 1 Using 0 06 Specific Gravity Gas and a pressure drop of 0 3 of Water Column 2 To obtain equivalent length of pipe add total length of pipe plus 3 for each 90o elbo...

Page 15: ...15...

Page 16: ...16...

Page 17: ...the upper brackets must be removed from the holes in the right side and placed in the holes on the left side of the upper brackets 4 The aquastat immersion well must be moved to the upper left rear t...

Page 18: ...et aquastat high limit between 180o F and 200o F 12 Turn service switch on Burner should start On one pipe fuel system only you may have to bleed the oil system To bleed attach a clear plastic tube to...

Page 19: ...2 80 2 0 150 PSI 12 0 11 0 Beckett CF375 1 35x45o B 9 0 1 00 150 PSI 12 0 11 0 Preliminary Gas Burner Settings Boiler Burner Gas Type Orifice Manifold Pressure Air Setting CO2 Draft Flue SL375 Carlin...

Page 20: ...eezes are toxic substances 11 Check the piping system for leaks and repair as required This will prevent water turnover with consequent risk of scale formation and corrosion in the boiler room 12 Chec...

Page 21: ...5 552815 552815 552815 11 1 Drain Valve 3 4 327998 327998 327998 327998 327998 12 1 Street Elbow 3 4 328002 328002 328002 328002 328002 13 1 Relief Valve 3 4 Female 570181 570181 570181 570181 570181...

Page 22: ...osits or corrosion in or on the cast iron sections 6 This warranty applies only to boilers installed in the United States 7 In order for this warranty to be effective a The boiler must have been insta...

Page 23: ...spill switch Oil Burner Operation Burner Model __________________ Nozzle _______GPH _______Deg ____Type_______ Burner Pump Pressure ______________ Fuel filter and fuel lines installed and inspected as...

Page 24: ...___________________________________________ Purchaser s Address ________________________________________________________________________ _______________________________________________________________...

Reviews: