Installation Clearances 

 

                     Boilers in rooms shall be installed with the clearances from combustible materials not 
less than indicated below.  Combustible materials are those made of or surfaced with wood, 
compressed paper, plant fibers, plastics, or other material that will ignite and burn, whether flame 
proofed or not, or whether plastered or not. 

 

The boiler must not be installed on combustible flooring.  The boiler is approved for installation on 
non combustible flooring only.  The boiler must not be installed on carpeting or vinyl flooring 

 

 

Minimum clearances to combustible construction are as follows: 

 

TOP - 6 IN. 

FRONT - 12 IN. 

FLUE CONNECTOR SINGLE WALL VENT PIPING - 9 IN. 

FLUE CONNECTOR DOUBLE WALL INSULATED DIRECT VENT PIPING – 2” 

REAR - 2 IN. 

SIDES - 2 IN. 

 

Consult NFPA-31 for construction techniques where the above minimum clearances cannot be obtained  

 

Minimum recommended clearances for service and access are as follows

 

TOP - 24 IN. 

FRONT - 24 IN. FROM BUNER 

FLUE CONNECTOR - 9 IN. 

REAR - 18 IN. 

SIDES - 12 IN. 

 

Note

:  When installed in a utility room, the door should be wide enough to allow the largest boiler part to 

enter, or to permit replacement of another appliance such as a water heater. 

 

Ventilation and Combustion Air 

 

                                                                                                                 
Warning…

Air openings to combustion area 

MUST NOT BE OBSTRUCTED

.  Adequate 

combustion air must be supplied at all times. 
 

 

Ventilation of boiler room must be adequate enough to provide sufficient air for combustion. 

 

When a boiler is located in an unconfined space in a building of conventional frame or masonry construction 
infiltration may provide adequate air for combustion and ventilation. If there is any doubt, install air supply 
provisions for combustion and ventilation in accordance with section 5.3, Air for Combustion and 
Ventilation, of the NFPA54  code, it is recommend that you follow, the applicable provisions of the local 
building codes as well.  

 

When a boiler is installed in a confined space, in a building of unusually tight construction, air for 
combustion and room ventilation must be obtained from the outdoors or from spaces freely communicating 
with the outdoors.  A permanent opening or openings having a total free area of not less than 1 square inch 
per 5,000 BTU per hour of total input rating of all appliances shall be provided. Ducts may be used to convey 
make-up air from the outdoors and shall have the same cross-sectional area of openings to which they are 
connected. 

 

When air for combustion and room ventilation is from inside buildings, the confined space shall be provide 
with two permanent openings, one starting 12 inches from the top and one 12 inches from the bottom of the 
enclosed space.  Each opening shall have a minimum free area of 1 square inch per one thousand (1,000) 
BTU per hour of the total input rating of all appliances in the enclosed space, but must not be less than one      

WARNING

Summary of Contents for SL375 THRU

Page 1: ...ATOR S MANUAL SL375 THRU SL7175 CAST IRON BOILERS Keep these instructions with the boiler at all times for future reference BOYERTOWN FURNACE CO PO Box 100 BOYERTOWN PA 19512 1 610 369 1450 www boyert...

Page 2: ...erty damage Your oil fired boiler is designed to burn No 1 and No 2 heating oil only Never use gasoline or a mixture of gasoline and oil Do not store gasoline or other flammable vapors and liquids in...

Page 3: ...n Tanks Venting Systems 8 Chimney Venting Direct Venting Burner Installation 13 Oil Tank and Piping 13 Gas Piping 14 Wiring 14 Swing Door 17 Opening the Door Closing the Door Door Hinge Reversal Opera...

Page 4: ...19 1 4 19 1 4 22 3 4 22 3 4 26 1 4 26 1 4 29 3 4 33 1 4 Supply Outlet Height 25 3 8 25 3 8 25 3 8 25 3 8 25 3 8 25 3 8 25 3 8 25 3 8 Return Outlet Height 4 1 2 4 1 2 4 1 2 4 1 2 4 1 2 4 1 2 4 1 2 4 1...

Page 5: ...all times Ventilation of boiler room must be adequate enough to provide sufficient air for combustion When a boiler is located in an unconfined space in a building of conventional frame or masonry con...

Page 6: ...wn it may be assumed that wood louvers will have 20 25 free area and metal louvers and grills will have 60 75 free area Louvers and grills shall be fixed in the open position or interlocked with the b...

Page 7: ...BY TECHNICALLY QUALIFIED SERVICEMEN SOLAIA BOILERS HAVE A MAXIMUM OPERATING PRESSURE OF 58PSI NOTE If normal operating pressures are greater than 30psi please contact the manufacturer for required tri...

Page 8: ...in to conform to code standards Discharge piping from the relief valve must be piped to a drain or must terminate 6 above the floor to eliminate damage to the structure or personal injury It must not...

Page 9: ...he boiler should comply with applicable building codes such as NFPA 211 An additional listed lining may be required to reduce transient low draft during startup and acid water condensation during cycl...

Page 10: ...he chimney must be made above the bottom of the chimney to avoid blockage Vent piping should extend just into the chimney far enough to expel flue gasses Inserting the vent piping too far into the chi...

Page 11: ...system must conform to the following guidelines See figure on following page a The vent terminal shall not be less than 3 feet above any forced air inlet to the house b The vent terminal shall not be...

Page 12: ...ANCE TO COMBUSTIBLE MATERIALS FROM THE DOUBLE WALL INSULATED VENT PIPING IS 2 CONSULT NFPA 31 FOR REDUCED CLEARANCES The air intake must be installed to the air inlet collar on the combination vent ho...

Page 13: ...correct nozzle is properly installed in the burner as shown in the preliminary burner settings and that the burner electrodes are adjusted as per the burner manual When using the Beckett AFG Carlin EZ...

Page 14: ...00 242 000 180 100 000 255 000 Note 1 Using 0 06 Specific Gravity Gas and a pressure drop of 0 3 of Water Column 2 To obtain equivalent length of pipe add total length of pipe plus 3 for each 90o elbo...

Page 15: ...15...

Page 16: ...16...

Page 17: ...the upper brackets must be removed from the holes in the right side and placed in the holes on the left side of the upper brackets 4 The aquastat immersion well must be moved to the upper left rear t...

Page 18: ...et aquastat high limit between 180o F and 200o F 12 Turn service switch on Burner should start On one pipe fuel system only you may have to bleed the oil system To bleed attach a clear plastic tube to...

Page 19: ...2 80 2 0 150 PSI 12 0 11 0 Beckett CF375 1 35x45o B 9 0 1 00 150 PSI 12 0 11 0 Preliminary Gas Burner Settings Boiler Burner Gas Type Orifice Manifold Pressure Air Setting CO2 Draft Flue SL375 Carlin...

Page 20: ...eezes are toxic substances 11 Check the piping system for leaks and repair as required This will prevent water turnover with consequent risk of scale formation and corrosion in the boiler room 12 Chec...

Page 21: ...5 552815 552815 552815 11 1 Drain Valve 3 4 327998 327998 327998 327998 327998 12 1 Street Elbow 3 4 328002 328002 328002 328002 328002 13 1 Relief Valve 3 4 Female 570181 570181 570181 570181 570181...

Page 22: ...osits or corrosion in or on the cast iron sections 6 This warranty applies only to boilers installed in the United States 7 In order for this warranty to be effective a The boiler must have been insta...

Page 23: ...spill switch Oil Burner Operation Burner Model __________________ Nozzle _______GPH _______Deg ____Type_______ Burner Pump Pressure ______________ Fuel filter and fuel lines installed and inspected as...

Page 24: ...___________________________________________ Purchaser s Address ________________________________________________________________________ _______________________________________________________________...

Reviews: