46
SPECIFICATIONS
•
General & Environmental
Units
Configuration
Unit Rating
kVA
12
16
20
20
kW
8.4
11.2
14
16
Conducted and Radiated EMC Levels
FCC Part 15, Class A
Compliant Safety Standards
UL 1778; c-UL
Compliant Immunity Standards
IEEE C62.41, Category B
Mechanical
Units
Dimensions
Width
in (mm)
20 (508)
Depth
28 (711)
Height
54 (1372)
Environmental
Units
Operating Temperature (max)
C (F)
0° - 40° (32° - 104°)
Relative Humidity
%
0-95% non-condensing
Maximum operating altitude
M (Ft)
3,000 (10,000)
Nominal heat dissipation
BTU/Hr
3,186
4,248
5,903
6,748
Acoustic noise level
dBA
<62 @ 1 meter
Input Data
Units
Nominal input voltage
VAC
208 or 240
Voltage Range (Typical)
208VAC nominal: operating voltage range shall be vari-
able based upon output loading percentages
% UPS Load
Input Voltage
80 – 100%
170 VAC
60 – 80%
144 VAC
30 – 60%
127 VAC
0 – 30%
110 VAC
Power factor
Cos Ø
>.98
Input frequency (nominal)
Hz
60
Input frequency range
Hz
40-70
Battery Module
Units
Number of lead acid batteries
10
Number of battery cells
60
Battery capacity
A/hr
9
Autonomy time (full load)
minutes
6
(With an equal number of Battery & Power Modules,
in a non-redundant configuration)
Maximum charge current (full load)
A
3
Nominal Voltage
VDC
120
Recharge Time
Hrs
>6 (to 90% capacity)
Output Data
Units
Output voltage
VAC
208/120 or 240/120
Voltage regulation
%
±3
Voltage stability (100% step load)
%
±7
Recovery time
msec
96
Voltage distortion
%
<3 THD, linear load
<7 THD, non-linear load
Output frequency
Hz
60
Efficiency at 100% load
%
89
Output overload capability
%
110 - 125% for 10 min
126-150% for 10 sec
151 - 200% for 2 cycles
Summary of Contents for S5K
Page 1: ...S5K Modular UPS USER MANUAL 208 240V 60Hz 12 to 20 kVA...
Page 2: ......
Page 7: ...3 Introduction General Description Modes of Operation Major Components...
Page 14: ...10...
Page 15: ...11 Installation Preparation Unloading Cable Installation Communications...
Page 23: ...19 Operating Instructions Controls and Indicators Operating Procedures Main Menu...
Page 39: ...35 Troubleshooting Alarm Messages Module LED Indication Module Replacement...
Page 46: ...42...
Page 47: ...43 Maintenance Proper Care Scheduled Maintenance Replacing Fan Filters...
Page 49: ...45 Reference Specifications Battery Run Times Warranty...
Page 54: ...50...
Page 55: ......