39
MODULE LED INDICATION
Every Battery, Power and Control Module features two LEDs to help inform the user of the module status.
Refer to the chart below for details.
Status LED
(Green)
Fault LED
(Amber)
Module Status
OFF
OFF
Module not inserted into frame.
System is OFF.
OFF
ON
Module is initializing (max 30 seconds*).
FLASHING
OFF
Normal Operation
FLASHING
FLASHING
Module is in start-up qualification mode or module warning. **
FLASHING
ON
Module failed, is off-line and module control is functioning.
OFF
FLASHING
Abnormal operation, re-insert module.
If this persists, contact Sola/Hevi-Duty at 1-800-377-4384.
ON
OFF
ON
ON
ON FLASHING
* If this persists for more than 30 seconds, check to verify the lever is in the down position, otherwise the module
is faulty.
** If both green and amber LEDs are flashing for more than 30 seconds, then reinsert module.
Status LED
Fault LED
Control Module
Status LED
Fault LED
Status LED
Fault LED
Battery Module
Power Module
Summary of Contents for S5K
Page 1: ...S5K Modular UPS USER MANUAL 208 240V 60Hz 12 to 20 kVA...
Page 2: ......
Page 7: ...3 Introduction General Description Modes of Operation Major Components...
Page 14: ...10...
Page 15: ...11 Installation Preparation Unloading Cable Installation Communications...
Page 23: ...19 Operating Instructions Controls and Indicators Operating Procedures Main Menu...
Page 39: ...35 Troubleshooting Alarm Messages Module LED Indication Module Replacement...
Page 46: ...42...
Page 47: ...43 Maintenance Proper Care Scheduled Maintenance Replacing Fan Filters...
Page 49: ...45 Reference Specifications Battery Run Times Warranty...
Page 54: ...50...
Page 55: ......