37
Power Module Warning
Something abnormal occurring
Match module serial number to serial number in
Alarm Log or Event Log, Contact qualified assis-
tance
Battery Module Warn
Something abnormal occurring
Match module serial number to serial number in
Alarm Log or Event Log, Contact qualified assis-
tance
Main Control Warning
Something abnormal occurring
Match module serial number to serial number in
Alarm Log or Event Log; contact qualified assis-
tance
Main Control Failure
Main Control Module has failed
Refer to Module LED indication section for correc-
tive action
Redund. Control Warn
Something abnormal occurring
Match module serial number to serial number in
Alarm Log or Event Log, Contact qualified assis-
tance
Redund. Control Fail
Redundant Control Module has
failed
Refer to Module LED indication section for correc-
tive action
Output exceeds max
load setting
Max load alarm is enabled, and
the load is greater then the value
set
None, if additional load is not added
Switch To Manual
Bypass
The switch on the only good SC
has been lifted. Informs user that
they should switch to bypass to
avoid dropping the load when the
pull the SC out.
Close manual bypass switch.
Battery Module Not
Ready
A Battery Module is not ready
and should be blinking it's yellow
LED.
Ensure module is fully seated and locked into
place. Refer to Module LED indication section for
corrective action.
Power Module Not
Ready
A Power Module is not ready and
should be blinking it's yellow
LED.
Ensure module is fully seated and locked into place
and lock lever is down. Refer to Module LED indi-
cation section for corrective action.
Load Exceeds Battery
Module Capacity
Occurs when there are no exter-
nal, extended, or normal Battery
Modules in the system, or when
the load is too great for the active
Battery Modules to support
Check the number of Battery Modules installed and
the power required by the connected load.
Bypass source not qual-
ified
The utility is out of range, unit will
not go to automatic bypass.
Check utility supply.
UPS switched from
bypass to inverter
The UPS switched from auto-
matic bypass to normal opera-
tion.
None
UPS on manual bypass
The user has put the unit on
manual bypass with the breaker
on the bottom front of the unit.
None
CAN Communications
Timeout
A module in the system has
timed out
See Event log
Turn SW2 off before
removing
Bypass source is not qualified or
the output is off, and lever on the
last good SC has been lifted.
This warning is to shut down the
unit with the rear rocker switch
before pulling out the SC.
Switch SW2 off
Alarm Message
Cause
Action
Summary of Contents for S5K
Page 1: ...S5K Modular UPS USER MANUAL 208 240V 60Hz 12 to 20 kVA...
Page 2: ......
Page 7: ...3 Introduction General Description Modes of Operation Major Components...
Page 14: ...10...
Page 15: ...11 Installation Preparation Unloading Cable Installation Communications...
Page 23: ...19 Operating Instructions Controls and Indicators Operating Procedures Main Menu...
Page 39: ...35 Troubleshooting Alarm Messages Module LED Indication Module Replacement...
Page 46: ...42...
Page 47: ...43 Maintenance Proper Care Scheduled Maintenance Replacing Fan Filters...
Page 49: ...45 Reference Specifications Battery Run Times Warranty...
Page 54: ...50...
Page 55: ......