8 • Wiring Diagram
________________________________________________________________________________________________
4.2
Medium voltage wiring diagram
Notes:
(1) – The optional communication RS485 output is an isolated output.
Use shielded twisted pair for RS485 communication.
It is recommended to ground the shield near the MIP-6.
(2) – The optional analog output is an isolated output.
Use shielded twisted pair for analog output.
It is recommended to ground the shield of the analog output cable at the receiver side.
(3) – All output relays are programmable. Refer to section
6.9.2 page 20 for more details.
(4) – All input relays are programmable. Refer to section
6.9.2 page 20 for more details.
(5) – RU7 is applicable for voltage up to 7.2kV.
RU13 is applicable for voltage up to 13.8kV.
(6) – Use medium voltage leads to connect the RU7/13 to the M.V. motor.
(7) –Use two ground connection to ground the RU7/13.
(8) – Use low voltage leads from RU7/13 to MIP-6 unless these leads run near M.V.
exposed equipment.
(9) – Leave terminal 53 not connected.