25 • Control Keypad
________________________________________________________________________________________________
6.9.5
Measured data – page 5
MEASURED DATA
--****--
Display
Description
INSULATION RES.
34377 KOHM
Displays the actual measured value of the resistance.
Range: 0kOhm – 60000kOhm.
1HOUR AVG. INSUL
23456 KOHM
Displays the average measured resistance of the last 1 hour.
Range: 0kOhm – 60000kOhm.
24HOUR AVG. INSUL
24456 KOHM
Displays the average measured resistance of the last 24 hours.
Range: 0kOhm – 60000kOhm.
PREV. MONTH AVG.
34566 KOHM
Displays the average measured resistance of the previous month.
Range: 0kOhm – 60000kOhm.
THIS MONTH MIN.
12345 KOHM.
Displays the
minimum
measured resistance of this month.
Range: 0kOhm – 60000kOhm.
THIS MONTH MAX.
4321 KOHM.
Displays the
maximum
measured resistance of this month.
Range: 0kOhm – 60000kOhm.
MINIMUM INSUL. R
34521 KOHM.
Displays the minimum resistance measured since last reset.
To reset this value, push the Reset button for more then 0.5 sec.
Range: 0kOhm – 60000kOhm.
MAXIMUM INSUL. R
99888 KOHM.
Displays the maximum resistance value measured since last reset.
To reset this value, push the Reset button for more then 0.5 sec.
Range: 0kOhm – 60000kOhm.
IN # 1 2 3 4 5 6
0 1 1 0 0 0
Displays a status indication of the six digital inputs.
“0” indicates open, “1” indicates closed.
OUT # 1 2 3 4 5 6
0 1 1 0 0 0
Displays a status indication of the six digital outputs.
“0” indicates open, “1” indicates closed.
TOTAL MEASURE T.
2 HOURS
Displays total hours of active insulation measurement.
Range: 0 – 65000. At 65000 this parameter is resets to zero. (approx. 7.4 years)
TOTAL # OF TRIPS
0
Displays total number of trips.
Range: 0 – 65535.