SOFAR 3.3~12KTLX-G3
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd.
- 23 -
4.Electrical Connection
Outline of this Chapter
This section introduces the electrical connection for the product. Please read the
information carefully, it will be helpful to understand the grounding, DC input,
AC output and communication connections and requirements.
Caution:
Before performing any electrical connections, ensure the DC switch is OFF and
AC circuit breaker is OFF. Allow up to 5 minutes for the capacitor to be
discharged.
Installation and maintenance should be done by certified
electrical engineer
Attention
Before the electrical connection, use opaque material to cover
the PV modules or disconnect PV string DC switch. PV arrays
will produce dangerous voltage if it is exposure under sun
Danger
For this product, the open circuit voltage of PV strings should
not greater 1100V
Note
The connected panel must meet the standard IEC61730A
。
String
Model
Isc PV(maximum)
Maximum output current (A)
SOFAR 3.3KTLX-G3
22.5A/22.5A
5A
SOFAR4.4KTLX-G3
22.5A/22.5A
6.7A
SOFAR 5KTLX-G3-A
22.5A/22.5A
7.6A
SOFAR5.5KTLX-G3
22.5A/22.5A
8.3A
SOFAR 6.6KTLX-G3
22.5A/22.5A
10A
SOFAR 8.8KTLX-G3
22.5A/22.5A
13.3A