SOFAR 7K~10.5KTLM-G3
User manual
Copyright © Shenzhen SOFAR SOLAR Co., Ltd
- 36 -
To obtain grid information via Plan A:
Connect the wires according to the wiring method as shown in "Figure 4-16 Plan
A”, and enable Anti-Reflux Power function and set the Reflux Power limit on
the menu interface of the machine. Hard Anti-Reflux also needs to be enabled to
take effect. Refer to <6.3 Main interface→1 Enter Setting→10.Set Reflux P> in
this manual for specific operation methods. If Plan A is selected, Select CT from
<6.3 Main Interface →1 Enter Setting→ 13.PCC Select>
To obtain grid information via Plan B:
Wiring according to the wiring method as shown in "Figure 4-16 Plan B”, The
setting of Anti-Reflux Power function is the same as that of Plan A. The
electricity meter function will also need to be enabled via the menu interface of
the machine. Refer to <
6.3 Main interface→A Enter Setting
> in this manual for
specific operation methods. If Plan B is selected, Select Meter from <6.3 Main
Interface
→
1 Enter Setting
→
13.PCC Select>
Please Note:
Anti-Reflux Function = Export Limit function
Reflux Power = Export Power
Hard Anti-Reflux control = Hard Export limit control
Anti-Reflux Control = Soft Export limit control
When Anti-Reflux function is enabled, the reflux power of point of common
coupling (PCC) will be limited to the set Reflux Power limit. Both Hard
Anti-Reflux Control and Anti-Reflux Control can be used together. However,
when Hard Anti-Reflux control is enabled, Anti-Reflux power limit cannot
exceed the Hard Anti-Reflux power limit. If the Anti-reflux power exceeds the
Hard Anti-Reflux power limit, the limit value is reported to trigger the overload
protection.