MASTERYS IP+
40-60 kVA 3/1
IT
ALIANO
ENGLISH
34
IOMMASIPXX07-GB 02
PRESENT CONFIGURATIONS menu
A Parameter
Description
Allowed values
• BATTERY RECHARGE
Sets the recharge voltage compensation value
YES/NO
TEMP COMPENSATION
according to the battery temperature (not present
with external battery cabinets.
• BACKFEED TYPE
Sets the type of backfeed protection.
DISABLE
BY-PASS-INPUT
ALONE
BY-PASS-INPUT
COMMON
• BATTERY TEST
Sets the frequency rate of the battery test in days
0÷180
TEST EVERY XX DAYS
(zero = do not perform the test).
• LAN IP STATICO
Sets the static IP address of the LAN
255.255.255.255
XXX . XXX . XXX .XXX
• SERIAL LINK JBUS
Sets the mimic panel jbus node
1÷15
SLAVE
NUMBER
DATE AND TIME
Sets the date and time
DD/MM/YY HH:MM
• EXTENDED COMMAND
Enables/Disables the mimic panel extended commands
YES/NO
• REMOTE COMMAND
Enables/disables the remote controls
YES/NO
BUZZER
Enables/Disables the buzzer
YES/NO
LCD CONTRAST
Sets the LCD display contrast
0/100
• STATISTICS PERIOD
Indicates the time in weeks for the calculation of statistics
1÷10
• GSS TIME DELAY
Sets the generator start up delay time (visible only when
1÷60 MINUTES
the GSS PCB is installed)
E-SERVICE TYPE
Select e-service operating mode
NONE, MODEM, SMS
E-SERVICE TELEPHONE
Insert the phone number to call for e-service messages
MAX 20 CHARACTERS
NUMBER
MENU
8