24
MASTERYS
BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
5. MIMIC PANEL
5.1.8. Service
menu
This is used to change the configuration parameters, insert the warranty activation code and display the service code.
5.1.9. UPS SETTINGS menu
This is used to change the configuration parameters. Access is via the password
MAST
which is keyed in by using the
and
keys and
ENTER
to go on to the next letter.
UPS SETTINGS menu
Parameter
Description
Allowed values
SET LANGUAGE
Sets the required language
English, Français, Italiano,
Deutsch, Español
SET OUTPUT VOLTAGE
Sets the required output voltage value
208/220/230/240 V
SET OUTPUT FREQUENCY
Sets the required output frequency value
50/60 Hz
SET MODE CONVERTER
Sets whether or not the UPS has to operate as a
frequency converter
WARNING! Set only on UPS with mains power
(MAINS) and auxiliary mains (AUX MAINS) sepa-
rated and with the auxiliary mains (AUX MAINS)
disconnected! Do not set on UPS with common
mains lines as it could damage the load!
YES/NO
SET MODE AUTORESTART
Sets whether or not the UPS has to restart automatically
after shutdown due to minimum battery
YES/NO
SET BATTERY AVAILABLE
Set if battery is present
YES/NO
if YES:
- SET BATTERY TYPE
Selects the type of batteries used
Sealed
- SET BATTERY CAPACITY
Sets the battery capacity in Ah
9.5 – 1000 Ah
- SET CHARGER TYPE
Selects the type of recharge required
Auto, Float, int.
- SET BATTERY ELEMENTS
Set the number of battery elements
120-132
- SET BATT_TEST PERIOD
Sets the frequency rate of the battery test in days
0, 30, 60, 90, 120,150,180 (zero
do not perform the test) in days
SET BACKFEED
Sets the type of backfeed protection
Disable,
2.ByPass-Input alone,
3.ByPass-Input common
SERIAL LINK
Inserts the serial communication parameters:
- Serial Link Baud Rate
- Serial Link Parity
- Serial Link Bit Number
- Serial Link Stop Bits
When the data is confi rmed, the serial connection automatically
changes the confi guration without having to switch off the UPS.
1200/2400/4800/9600/14.4
odd/even/none
8-9
0-1
JBUS SETTING SLAVE NR.
Sets the mimic panel jbus node
When the data is confi rmed, the serial connection au-
tomatically changes the confi guration without having to
switch off the UPS.
1/32
DATE SETUP
Sets the date
DD/MM/YY
TIME SETUP
Sets the time
HH:MM
SYN EXT CMDS ENABLED
Enables/Disables the mimic panel extended commands
YES/NO
REMOTE CMDS ENABLED
Enables the transmission of commands from external systems YES/NO
SET BUZZER ENABLED
Enables/Disables the buzzer
YES/NO