22
MASTERYS
BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
5. MIMIC PANEL
5.1.4. Alarms
menu
This menu displays all alarms that are active at the time of access. The alarms menu is activated automatically when an alarm condition occurs.
ALARMS menu
Code
Mimic panel message
Description
A00
GENERAL ALARM
At least one alarm is present
A01
BATTERY ALARM
Battery circuit failure or faulty operation
A02
OUT OVERLOAD
Power required in output over the limits
A06
VAUX OUT OF TOL
The voltage or frequency limits accepted by the bypass have been exceeded
A07
OVER TEMPERATURE
Temperature excessive or ventilation problems
A08
MAINTEN. BYPASS
Active bypass procedure
A17
IMPROPER USE
Improper conditions of use verifi ed (load, mains, temperature)
A18
OVERLOAD OFF INV
Inverter shutdown due to overload
A20
WRONG CONFIG.
Error in the confi guration parameters (e.g. diff erent between several UPS units in parallel)
A22
MAINS OUT OF TOL
The voltage or frequency limits accepted by the rectifi er have been exceeded
A23
RECTIFIER ALARM
Rectifi er fault
A25
INVERTER ALARM
Inverter fault
A26
BATT CHARGER ALM
Battery charger fault
A29
BYPASS ALARM
Bypass fault
A30
OVERLOAD STOP
The duration of the overload has inhibited the bypass
A38
EXTERNAL ALARM1
Signalling from ADC input
A39
EXTERNAL ALARM2
Signalling from ADC input
A40
EXTERNAL ALARM3
Signalling from ADC input
A41
EXTERNAL ALARM4
Signalling from ADC input
A42
REMOTE SERVICE ALARM
This alarm indicates that a critical anomaly has occurred on the UPS.
Where a maintenance contract with the Remote Monitoring option is in
place, the procedure for analysing the UPS via remote connection will be
automatically activated by your service centre provider.
A43
REDOUNDANCY LOST
The power required by the load no longer allows the preset redundancy
N+x (signalling for UPS units in parallel) to be maintained
A44
SERVICE CHECK
Notifi cation that the routine service check is overdue
A49
BATT. DISCHARGED
The energy available in the battery has been depleted
A51
OPT. BOARD ALM
Fault in the optional cards in the slots
A58
ESD ACTIVATED
The remote emergency shutdown command has been activated
A59
BATT.CIRC. OPEN
The battery switch is open
A60
FAN FAILURE
Fans faulty or blocked
A61
PHASE ROT. FAULT
Wrong phase cycle direction