31
EN
5.4. Installing the unit
• UPS model
To keep air-flowing freely, it is recommended to keep a clearance with
500mm space both for front and rear side.
1.
Place the unit on a flat, stable surface in its final location.
2.
Install ‘stabilizer bracket’(if configured): remove side screws from the
unit, then install ‘stabilizer bracket’ to the unit.
3.
Fix the unito to ground if necessary: fix the brackets on the UPS.
Drill the floor (measure indicated in the picture below) and move
the UPS between the holes. Fix the UPS to the floor with bolts (M8
bolts are recommended).
285
325
250
83
Unit:mm
• EBM
Install the EBM model, refer to UPS model installation as above, place it next to UPS.
+ -
ESC
+ -
ESC