ITYS 6-10 kVA - 551431A - SOCOMEC
39
EN
7. UPS MAINTENANCE
7.1. Equipment care
For the best preventive maintenance, keep the area around the equipment clean
and dust free. If the atmosphere is very dusty, clean the outside of the system with
a vacuum cleaner.
For full battery life, keep the equipment at an ambient temperature of 25°C (77°F).
Note:
the batteries are rated for a 3-5 year service life. The length of
service life varies, depending on the frequency of usage and ambient
temperature. Batteries used beyond expected service life will often have
severely reduced runtimes. Replace batteries at least every 4 years to
keep units running at peak efficiency.
7.2. Transporting the UPS
Note:
please transport the UPS only in the original packaging. If the UPS
requires any type of transportation, check that the UPS is disconnected
and turned off.
7.3. Storing the equipment
If you store the equipment for a long period, recharge the battery every 6 months
by connecting the UPS to the mains power supply. It is recommended that the
batteries are charged for 48 hours after long-term storage.
If the batteries have not been charged over a six-month period, do not use them.
Contact your service representative.