74
DIRIS Digiware - 542875G - SOCOMEC
EN
The example below indicates that the load power P1 will be correctly calculated by associating current from the iTR
connected to input I03 with voltage V1 from the DIRIS Digiware U-xx module. This is not the case as per the red cells
showing the error is on inputs I03 and I01.
After clicking on "AutoCorrect" the association errors are corrected and there are no more red cells in the diagnostic table:
You can also correct the wrong voltage/current association manually in the "Current Sensors" menu: