55
DIRIS Digiware - 542875G - SOCOMEC
EN
9.1.2. DIRIS Digiware S
S-
xxx
S-
xxx
Power/communication
Voltage detection
USB
Addressing button
Main LED
Fixed
Blinking
Green
Product operating normally
When a communication frame is received is
processed
and
During 10 seconds, if an identification command is
initiated from the Easy Config System software
Red
Indicates the presence of a measurement alarm
(does not have priority over system alarms)
Indicates the presence of a system alarm (**)
Orange
Address conflict during Auto-Discovery process
Not available
I01, I02 & I03
LEDs (***)
Fixed
Pulse
Red
Indicates that no voltage is detected on a phase.
Corresponds to the metrological pulse weight
(1Wh by default)
(**) System alarms for the DIRIS Digiware S module can be a bad V/I association indicating a possible wiring error.
(***) By default, I01, I02, I03 LEDs are configured in voltage detection mode.
Settings can be changed to metrological LED mode from the Easy Config System configuration software.
The voltage detection feature is an indication of the presence or the absence of voltage on one of the phases. It
should only be used as an indication, and must not replace the use of a voltage tester.
In addition, the nominal voltage must be correctly configured in the DIRIS Digiware U module