11.3. Ethernet communication
The DIRIS Digiware M-50/M-70 gateway and DIRIS Digiware D-50/D-70 display can communicate over Ethernet using
multiple communication protocols (Modbus TCP, BACnet IP, SNMP v1, v2, v3 & Traps).
Example of architecture using an M-50/M-70 gateway:
U-xx
M-50/M-70
Ethernet
Digiware Bus
I-35
S-xx
Digiware bus
terminating resistor
11.4. Ethernet and RS485 communication
In the event that the system needs to communicate to a second PLC via RS485, you can configure M-50/M-70 gateways
and D-50/D-70 displays as RS485 slave to communicate via the RS485 bus in addition to the Ethernet bus.
Example of architecture using a D-50 or D-70 display:
DIRIS Digiware D-50/D-70
U-xx
RS485
Digiware Bus
I-35
S-xx
Digiware bus
terminating resistor
Ethernet
The following rules must be observed:
- A 120 Ω resistor must be added at the start of the RS485 link
- A 120 Ω resistor must be added at the end of the RS485 link
- An end of line resistor must be added at the end of the Digiware bus.
11.5. Communication tables
The communication tables and associated explanations can be found on the documentations page for DIRIS Digiware on
the SOCOMEC website:
www.socomec.com/operating-instructions_en.html