socomec ENT-RK10 Product Manual Download Page 17

 

TECHNICAL DATA

 

Q

   

SECTION 1   

 

16 

 

7  

TECHNICAL 

DATA 

 

Technical data 

ENT-TW08 
 

ENT-TW10 
ENT-RK10 

ENT-TW15 
ENT-RK15 

ENT-TW20 
ENT-RK20 

Power 

800VA / 560W 

1000VA / 700W 

1500VA /1050W 

2000VA /1400W 

Technology 

VFI (Voltage and Frequency Independent) On line double conversion 

Input

 

Input voltage 

160 ÷ 276Vac (1ph)  

Frequency 50/60Hz 

(automatic 

selection) 

Power factor 

>0.97 

Input current 

Sinusoidal absorption 

Output

 

Output voltage (Vout) 

230V (1ph) 

±

 3% (selectable* 220/240V) 

Voltage distortion 

<4% on a linear load 

Output frequency stability 

50Hz or 60Hz (

±

 0.5% in battery mode) 

Automatic by-pass 

Voltage selected 

±

 15%  

Overload (with mains 
present) 

130% for 10 seconds 

AC/AC efficiency 

88%  

Crest factor 

3:1 

Reference normatives

 

Standard 

European UPS standard EN50091 and CE marking 

Safety / EMC standards 

EN50091-1-1 / EN50091-2 

Environmental data

 

Operating temperature 

0 +40°C (32-104°F)                 

for longer life battery from 15°C to 25°C (59°F - 77°F ) 

Storage temperature (MAX) 

-5 +50°C (23-122°F)  

Relative humidity HR 

0 ÷ 90% non-condensing 

Maximum altitude (above 
sea level) 

1,000mt (3,300ft) with no derating; maximum 3,000mt (10,000ft) 

Acoustic noise (ISO 3746) 

< 45dB @ 1mt 

Physical data (weight including batteries) 

 

Dimensions (WxDxH) TW  

145x405x225 mm 

87x495x435 

TW weight 

14 kg 

15 kg 

22 kg 

23kg 

Dimensions (WxDxH)  RK 

483x460x87 mm

483x495x87 mm 

RK weight 

16 kg 

22 kg 

23kg 

 
 
 

Summary of Contents for ENT-RK10

Page 1: ...UPS ENTERPRISE 800 2000 VA PRODUCT MANUAL...

Page 2: ......

Page 3: ...3 2 3 Putting an external battery expansion into operation 9 4 CONFIGURATION AND START UP 10 4 1 CONFIGURATION OF THE OUTPUT VOLTAGE BATTERY EXPANSIONS 10 4 2 Power Share Configuration 2000VA version...

Page 4: ...notification of the malfunction if it is not possible to provide proof of purchase the serial number and date of production will be used to calculate expiry of the warranty which may lead to a reduct...

Page 5: ...ppropriate procedure When assembling and replacing the battery the UPS should always be switched off and disconnected from the mains power supply The UPS contains an internal power source which is the...

Page 6: ...ed via a first AC DC conversion followed by a DC AC conversion in order to provide the consumer a stable waveform that is exempt of noise or distortions and therefore completely independent of the inp...

Page 7: ...e buzzer reset alarms OFF Off button inverter OFF LED 1 Battery capacity LED bar LED 2 GREEN Mains up and regular LED 3 YELLOW Auxiliary mains present and regular bypass line LED 4 RED General alarm s...

Page 8: ...ow for adequate ventilation and access to the rear panel Make sure not to set the UPS or any other heavy object on the cables Check that the voltage and frequency preset for operation is right for you...

Page 9: ...e standards in force A distribution panel must be set up if there is not one already which can be used to isolate the mains upstream of the UPS This panel must have an automatic switch of sufficient c...

Page 10: ...ure that the safety switch on the battery expansion is in the OFF position during the connection steps Set the battery expansion unit beside the UPS on the side that does not have the air vents Connec...

Page 11: ...mode within 10 seconds In output voltage setting mode as well as the battery LED bar the no break output LED also flashes For configuration of the voltage use the same arrangements as for the battery...

Page 12: ...lication is powered by the UPS and continuous power is guaranteed If the UPS is switched on with mains absent follow the same procedure as described above and after the self test the UPS will go into...

Page 13: ...no longer be muted It is recommended to close down applications manually if the automatic shutdown procedure has not been activated via the specific software installed on the computer WARNING your ap...

Page 14: ...ation of performance 5 1 4 Switching the UPS off Partial switching off with mains present Pressing the OFF key for 2 sec in normal operation with mains present activates the partial switching off of t...

Page 15: ...ions on the leading operating systems based on JSC Java Shutdown Client Net Vision Web SNMP manager for control via LAN with TCP IP protocol and remote shutdown management the relay card with 3 zero p...

Page 16: ...ica Gestione Rel R1 R2 R3 Rel Uscite Rel I1 Ottici Ingresso 9 PIN The maximum voltage that can be applied to the contacts is 60Vdc and the maximum current is 500mA Pin DB 9 Signals NC NO JUMPERS 4 Gen...

Page 17: ...atic by pass Voltage selected 15 Overload with mains present 130 for 10 seconds AC AC efficiency 88 Crest factor 3 1 Reference normatives Standard European UPS standard EN50091 and CE marking Safety E...

Page 18: ...ted Insert the main switch Mains voltage is missing Have an electrician check the mains The MAINS LED does not come on the acoustic alarm sounds at intervals Fuse on the input faulty Replace the fuse...

Page 19: ...Q VIEW SECTION 4 800 VA 1000 VA tower front view rear view Battery extension tower 1000 VA rack 19 Battery extension rack 19 Rear view Front Rear view 4 2 1 7 5 6 8 5 6 5 7 1 4 2 5 8 5...

Page 20: ...VIEW SECTION Q 5 1500 2000 VA tower Battery extension tower rear view rear view 1500 2000 VA rack 19 Rear view Battery extension rack 19 Rear view 2 7 1 6 4 5 3 5 3 4 1 5 5 5 5 6 8 2 7 5...

Page 21: ...3 Presa di uscita power share 4 Connettore seriale RS232 USB DB9 5 Connettore batteria per espansione esterna 6 Presa di uscita per utenze 7 Presa ingresso rete e fusibile 8 Interruttore batterie 1 L...

Reviews: